Technician settings (Cont’)
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROBOX3/3C/5
-TRACE
Owner’s manual & Technician Settings
Pg. 11
P05 – Heaters cycle and splitting time
Press the [SELECT] and [+] buttons simultaneously.
“P05”, “SP” and the splitting time will appear on display.
The minutes will blink.
The heaters cycle / splitting time parameter defines the working time of the
heaters when working in sequence.
Example: the splitting time is set to 10 minutes and 4 heaters work in
sequence, each heater will be ON for 2.5 minutes (10/4=2.5).
Use the [+] and [-] buttons to adjust the splitting time.
Range: 10...1999 minutes
Default: 60 minutes.
Splitting time
Cont’
P06 – Enable/Disable Temperature sensor / Aquastat logic
Press the [SELECT] and [+] buttons simultaneously.
“P06” and the number “0” or “1” will appear on display.
Use the [+] and [-] buttons to select between:
“0” - Logic set by both TEMPERATURE SENSOR
and AQUASTAT (default).
“1” - Logic set by TEMPERATURE sensor only.
“2” - Logic set by AQUASTAT sensor only
Logic by
temperature
sensor only
Logic by
temperature
sensor and
aquastat
Logic by aquastat
sensor only
P04 - Manual mode ON time
Press the [SELECT] and [+] buttons simultaneously.
“P04”, “On” and the time “Manual ON” mode time period will appear on
display. The hours will blink.
The delay time parameter defines a time frame in which the heaters remain
ON after receiving an “Manual ON” command.
Use the [+] and [-] buttons to adjust the hours of the working time.
Range: 00...99 hours
Default: 03 hours
Press the [SELECT] and [+] buttons simultaneously again.
The minutes will blink.
Use the [+] and [-] buttons to adjust the minutes of the working time.
Range: 00...59 minutes
Default: 00 minutes
Manual ON
(minutes)