Technician settings (Cont’)
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROBOX3/3C/5
-TRACE
Owner’s manual & Technician Settings
Pg. 13
P09 - Test conditions mode / Technician commissioning mode
Turn ON test conditions to check the functionality of the system regardless of
temperature sensors parameters (i.e. during the summer).
In test conditions, the Ambient temperature is always -7°C/19°F.
Press the [SELECT] and [+] buttons simultaneously.
“P09” will appear on display. The hours will blink.
Use the [+] button to enter test/commissioning mode – the word “Test” will
appear on display.
Use the [-] button to manually exit test/commissioning mode – the word
“Test” will disappear from display.
Note: If the technician did not manually exit test/commissioning mode, the unit
will automatically return to normal mode after 5 hours.
Test
conditions
mode
Restore default values
Move DIP switch S1 to ON position.
Press and hold the [ON] button for 10 seconds. The thermostat will beep.
Move DIP switch S1 back to OFF position.
In order to save changes and return to normal display, move DIP switch S1 back to
OFF position.
Save changes and return to normal display
Important: Changes made to technician parameters will not take effect as
long as DIP switch S1 is in ON position.