background image

Technician settings (Cont’)

Tel: (856) 2882882

Tel: +972-3-9626462

Fax: +972-3-9626620

support@meitavtec.com

PYROBOX3/3C/5
-TRACE

Owner’s manual & Technician Settings

Pg. 15

Follow the steps below to enable or disable each of the 5 zones.
By default, all zones are enabled.
1. Turn the thermostat OFF. 
2. Press and hold both the [+] and the [-] buttons simultaneously for 10 seconds.
3. Choose the required zone using the [Select] button. Selected zone number will appear on display 

and the heater icon will flash.

4. Use the [+] button to enable the selected zone (black heater icon).
5. Use the [-] button to disable the selected zone (white heater icon).
6. Repeat steps above 3 to 5 for any required zone.
7. Press and hold both the [+] and the [-] buttons simultaneously again for 5 seconds to return to 

normal display.

Enable/Disable zones

[+] & [-]

(10 sec.)

[Select]

[Select]

[Select]

5

4

3

2

1

[-]

[+]

[-]

[+]

[-]

[+]

[-]

[+]

[-]

[+]

[Select]

[+] & [-]

(5 sec.)

Black icon  – Zone enabled

White icon  – Zone disabled

Summary of Contents for PYROBOX3-TRACE

Page 1: ...PYROBOX3 TRACE PYROBOX3C TRACE PYROBOX5 TRACE Installation and Operating manual ...

Page 2: ...ing time 11 P06 Enable Disable 2nd temperature sensor Aquastat 11 P07 Heater outputs logic by Temperature sensor or by Aquastat 12 P08 MODBUS MAC Address for building automation option 12 P09 Test conditions mode 13 Save changes and return to normal display 13 Restore default values 13 DIP Switch settings 14 DIP switch S2 Short measuring times test only 14 DIP switches S3 and S4 heaters sequencing...

Page 3: ...ilable electrical power The PYROTRACE offers various operating and programming options such as Switchable temperature scales F or C Adjustable Lower ambient temperature limit to stop Both Automatic and Manual modes heaters lockout Adjustable heaters cycle and splitting times Energy saving temperature limit Adjustable heaters hold on off delay Commissioning Test environment Tel 856 2882882 Tel 972 ...

Page 4: ...the main breakers fuses are suitable for the heating systems rating 80 load Grounding means must comply with local regulations and CEC NEC Ensure that the heating system de icing system connected to this unit complies with the UL 499 or UL 515 CSA 22 2 130 3 standard and is certified listed by an NRTL Ensure that all wiring is rated for the application at 60 C 140 F as per UL 515 CSA 22 2 130 clau...

Page 5: ... Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com PYROBOX3 3C 5 TRACE Owner s manual Technician Settings Pg 5 2 1 A C C R C B R L1 N1 R GFCI Main supply 120 VAC F 5A R IN IN 1 2 Current transformer Transformer 130VA 120 24VAC 300 VAC max 30 AMP max Heater load connection L1 L2 L3 600 VAC max 50 AMP max per pole Branch circuit protection and disconnect provided by installer Max 60A Aquasta...

Page 6: ...882 Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com PYROBOX3 3C 5 TRACE Owner s manual Technician Settings Pg 6 Caution Incorrect voltage may cause fire or seriously damage the unit 2 1 A C C R C B R L1 N1 R GFCI F 5A R IN IN 1 2 Current transformer Transformer 130VA 120 24VAC Heater load connection L1 L2 L3 600 VAC max 50 AMP max per pole Internal connections Main supply 120 VAC Branch ...

Page 7: ...le Tel 856 2882882 Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com PYROBOX3 3C 5 TRACE Owner s manual Technician Settings Pg 7 2 1 A C C R C B R L1 N1 R GFCI Main supply 120 VAC F 5A R IN IN 1 2 Current transformer Transformer 130VA 120 24VAC Heater load connection 300 VAC max 30 AMP max Internal connections Internal connections Caution Incorrect voltage may cause fire or seriously damag...

Page 8: ... Selecting temperature scale Press the button for Celsius Press the button for Fahrenheit Tel 856 2882882 Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com PYROBOX3 3C 5 TRACE Owner s manual Technician Settings Pg 8 Heaters indication Heater ON Heater OFF The number beneath the heater icon indicate the heater stage 1 to 5 Stg 1 Stg 2 Stg 3 Stg 4 Stg 5 Black icon Heater ON White icon Heater...

Page 9: ...ime delay before stopping the heaters P04 ON time for manual mode P05 Heaters cycle time Splitting time P06 Enable Disable 2nd temperature sensor logic Aquastat P07 Heaters outputs logic P08 MODBUS MAC Address for home automation system option P09 Commissioning Test mode Restore defaults Move DIP switch S1 located on the side of thermostat to ON position Press the SELECT and buttons simultaneously...

Page 10: ... point temperature Note 2 The staggering sequence will continue during the time delay period Time delay minutes Cont P02 Lower limit temperature for heating Press the SELECT and buttons simultaneously P02 and the low limit temperature will appear on display When the temperature on the temperature sensor drops below the low temperature limit the heating system will stop Use the and buttons to adjus...

Page 11: ...the SELECT and buttons simultaneously P06 and the number 0 or 1 will appear on display Use the and buttons to select between 0 Logic set by both TEMPERATURE SENSOR and AQUASTAT default 1 Logic set by TEMPERATURE sensor only 2 Logic set by AQUASTAT sensor only Logic by temperature sensor only Logic by temperature sensor and aquastat Logic by aquastat sensor only P04 Manual mode ON time Press the SE...

Page 12: ...Temperature Sensor Aquastat Sensor 1 2 3 0 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 Option P08 MODBUS MAC Address Press the SELECT and buttons simultaneously P08 and the MODBUS MAC Address will appear on display Use the and buttons to set the MAC Address of the unit Setting the MAC address for the unit will make it available through the home automation system Range 0 60 Select 0 for NO COMMUNICATIO...

Page 13: ...test commissioning mode the word Test will appear on display Use the button to manually exit test commissioning mode the word Test will disappear from display Note If the technician did not manually exit test commissioning mode the unit will automatically return to normal mode after 5 hours Test conditions mode Restore default values Move DIP switch S1 to ON position Press and hold the ON button f...

Page 14: ... test only DIP switches S3 and S4 heaters sequencing logic Use DIP switches S3 and S4 to define the sequencing logic of the heater zones as follows S3 OFF S4 OFF All 4 outputs work per request from the temperature sensor S3 OFF S4 ON Outputs 1 3 and outputs 2 4 work together according to splitting time S3 ON S4 OFF Outputs 1 2 and 3 work in sequence according to splitting time and output 4 works c...

Page 15: ...or 10 seconds 3 Choose the required zone using the Select button Selected zone number will appear on display and the heater icon will flash 4 Use the button to enable the selected zone black heater icon 5 Use the button to disable the selected zone white heater icon 6 Repeat steps above 3 to 5 for any required zone 7 Press and hold both the and the buttons simultaneously again for 5 seconds to ret...

Page 16: ...tavtec com PYROBOX3 3C 5 TRACE Owner s manual Technician Settings Pg 16 Temperature Sensor error Error 2 Temperature sensor is not connected or short circuit SensErr 1 Will appear on display Communication error Error 1 MODBUS Communication error SensErr 1 Will appear on display ...

Page 17: ...0 Tripped relay LED indicator TRIPPED Remote C T PYROBOX3 3C 0 01 0 02 0 03 0 04 0 05 0 06 0 07 0 08 0 09 0 10 PYROBOX5 The GFCI ground fault circuit interrupter is designed to provide protection for electrical equipment The ON Time Delay and Current Trip should be configured to match application requirements DANGER HIGH VOLTAGE GROUND FAULT SENSOR GFCI TEST The GFCI should be tested monthly Press...

Page 18: ...Notes Tel 856 2882882 Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com PYROBOX3 3C 5 TRACE Owner s manual Technician Settings ...

Page 19: ...Notes Tel 856 2882882 Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com PYROBOX3 3C 5 TRACE Owner s manual Technician Settings ...

Page 20: ...Tel 856 2882882 Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com www meitavtec com ...

Reviews: