4. Technician settings (cont’)
- 32 -
P99 – One or Two set points (for cool and for heat)
“00” -
One set point for cooling and heating (default)
“01” -
two set points – one for cool and one for heat
P100 – Enable/Disable Screen dimming
“00” -
Enable
“01” -
Disable (default)
P101 – Screen dimming delay
Range: 0...99 minutes
Default: 5 minutes
P102 – Dimming percentage value
Range: 1,5,10...90%
Default: 10%
P105 – Display brightness
Range: 50...100%
Default: 100%
P188 – Room temperature limit for disabling dehumidification in
unoccupied mode
Range: 10...30ºC
Default: 18ºC