4. Technician settings (cont’)
- 33 -
P191 – Door switch/key-tag function for unoccupied mode
0 – Turn unit off
1 – Switch to economy set-points
2 – Air circulation – Fan on
P192 – Temperature set-point for re-heat in unoccupied mode
Range: 10...20ºC
Default: 20ºC
P189 – Dehumidification cycle in unoccupied mode
Range: 0...600 minutes
Default: 20 minutes
P190 – Dehumidification break time in unoccupied mode
Range: 0...900 minutes
Default: 40 minutes
P194 – Humidity differential band
Range: 0...10 %RH
Default: 5%RH
P195 – Humidity sensor reading offset
Range: -9…+9 %RH
Default: 0 %RH