- 22 -
4. Technician settings (cont’)
P17 – PIR (occupancy sensor) delay time
before switching to unoccupied mode (ON delay)
Range:
0…250 minutes, Default: 20 minutes
P19 – PIR (Occupancy sensor) polarity
“00” -
Normally open (default)
“01” -
Normally close
P25 – Economy set point for cooling
Range:
5…35°C / 41…90°F
Default: 30°C / 86°F
P26 – Economy set point for heating
Range:
5…35°C / 41…90°F
Default: 10°C / 50°F