2

Project

Indicators

Precision

Thermocouple ±

0.3%

input

range.Ambient

temperature compensation error

2

Thermal

resistant

± 0.5% input range

Isolation

The sampling channel is isolated from

the power supply, the sampling channel

is isolated from the output, and the

channels are isolated from each other

Note

: when the input type of channel 2 and channel 4 is 0, the

temperature control output OUT2 and OUT4 will be automatically

assigned to the refrigeration control output of channel 1 and channel 3;

If the input type of channel 1 to channel 4 is not selected as 0, and are

set to the heating and cooling control function, then the refrigeration

control of each channel can choose OUT5 ~ OUT12 to output, or

through the PLC read MTC #733 (refrigeration output state) register to

use the PLC I/O port output refrigeration control.

3. 3 Buffer Zone

BFM

MTC-04 Modbus or MCbus through the BFM and the main module

temperature data and other information exchange. Reading and writing

attributes of buffer can use MODBUS or MCBUS instructions for

reading and writing. If you read the reserve unit, will get zero value.

Save mark Y representative with the parameter save function, can be

flash memory, marked N said cannot be flash memory. Using MODBUS

agreement, most once writeable only 50 BFM unit. BFM unit part

content as follows:

1. The channel operation monitoring;

2. Channel characteristics set;

3. Control function setting;

4. BFM parameters save Settings

5. Other.

For more about the PID, set, alarm, MCbus and other related content

and routines, please refer to the MTC-04-NTR thermostat user manual

".

3. 3.1 The channel operation monitoring

MTC-04-NTR buffer (BFM) to monitor the operation of the channel

contents in Table 3-3.

Table 3-3 The channel operation monitoring of MTC-04-NTR buffe

BFM

BFM

Contents

Remarks

na

tur

e

Sa

ve

CH1 CH2 CH3 CH4

#701 #702 #703 #704 Measured value

PV

*1

Units: 0.1

and 0.1

R

N

#709 #710 #711 #712

Heat side

control output

(MV) * 2

The default

value: 0.0%

(percentage

show

R

N

#717 #718 #719 #720

More

paragraphs of

the currently

executing

period control *

3

Default value:

0.0%

(expressed as a

percentage)

R

N

#725 #726 #727 #728

Multi-step

control current

execution

segment * 3

Default value

0

Range:0~8

R

N

#733

Output state of

refrigeration

end *4

Default value

0

R

N

#734

Input port

status*5

Default value

0

R

N

#735

Error status

word * 6

Default value

0

R

N

#736

Set value range

error address*7

0:normal

Other values:

setting the

wrong BFM

address

R

N

#737

Cold junction

temperature*8

Default value

0 R

N

#738 #739 #740 #741

Work status

word * 9

Default value

0

R

N

* 1. #701 ~ #704:The measured value of channel 1 to channel 4. The

unit is determined according to the input type (#901 ~ #904). When the

mode is Celsius, the unit is 0.1

; when the mode is Fahrenheit, the

unit is 0.1

.

* 2. #709 ~ #712:Heating side control output value MV; #717 ~ #720:

cooling hot side control output value MV; The control output value of the

channel obtained by the control algorithm.

* 3. #725 ~ #728: Each channel multi-step setting executes the current

segment. The segment number being executed when multiple segment

Settings are displayed. 0: indicates that the execution state is not set in

multiple segments or that multiple segments are completed.

* 4. #733: Output status of refrigeration end. Bit0 corresponds to the

output state of the refrigeration end of channel 1, Bit1 corresponds to

the output state of the refrigeration end of channel 2, and so on. When

is 1, the output of the refrigeration end is effective; when is 0, the output

of the refrigeration end is invalid.

* 5. #734: Input port status. Bit0 corresponds to input port 1, Bit1 to

input port 2, and so on. A value of 1 indicates that the input is valid, and

a value of 0 indicates that the input is invalid.

* 6. The failure status information of #735 is shown in table 3-4.

Table3-4 BFM#735 State Information

A state of BFM#735 ON

1

OFF

0

b0

Error

When b1 ~ b15 any error occurs,

this flag is 1 (b1 ~ b2 in any

one of 1, stop all channel AD

converter)

Correct

b1

Save

b2

Hardware fault

AD converter or other hardware

failure

Hardware

normal

b3

Set value

backup error

When the interference and

the MTC due to an internal error

occurs, the flag will change

to 1. Then if you turn the

power off, still not be clear error,

please contact the sales agent or

our

Data

backup

normal

b4

The cold

junction

temperature

compensation error

b5

AD transform

digital range error

AD transform digital output value

is less than -1 or greater than

4096, the flag is 1

Digital

output

value is

normal

b6

Set data

recovery error

When the interference and

the MTC due to an internal error,

if error reading backup data, the

flag is 1

b7

Save

b8

b15 Broken

accidentally

detection (only

support

thermocouple)

1 ~ 4 channel thermocouple

broken accidentally, the flag is 1

No broken

accidentall

y wrong

channel

* 7. #736: error address setting value range. Incorrect BFM area code

is displayed.

* 8. #737: reflects the current cold end temperature.

* 9. #738 ~ #741: status word for each channel. Shows the error state

and control state of each channel, #738 corresponds to channel 1,

#739 corresponds to channel 2, and so on. See table 3-5 for specific

information.

Table 3-5 each channel error status and control of the state

Bite

Definition

ON

1

OFF

0

b0

b3

Alarm 1 ~ 4 state Alarm

No alarn

b4

Sign of

Initialization

complete

Initialization complete

Initialization

unfinished

b5

Auto-tuning state Self-tuning state

Status of no

self-tuning

b6

Control state

Control state

uncontrolled

state

b7

Control

completion status

The temperature reaches

setting and in a stable

state

Incomplete

control

b8

b15 Save