Specification
All quoted accuracies are at +20 °C.
Insulation
Range
Full Scale
Accuracy
(
BM80/2
&
BM82/2
only)
1000 V
200 G
Ω
± 2% ± 2 digits ± 0,2% per G
Ω
500 V
100 G
Ω
± 2% ± 2 digits ± 0,4% per G
Ω
250 V
50 G
Ω
± 2% ± 2 digits ± 0,8% per G
Ω
100 V
20 G
Ω
± 2% ± 2 digits ± 2,0% per G
Ω
50 V
10 G
Ω
± 2% ± 2 digits ± 4,0% per G
Ω
Notes:
All ranges measure from 0,00 M
Ω
upwards.
0 - 10 G
Ω
on analogue scale on all ranges.
Test voltage accuracy:
+15% maximum on open circuit
(250 V and 1000 V)
- 0% minimum on 1 mA load
(50 V and 100 V)
- 0% minimum on 250 k
Ω
load
Short circuit current:
< 2 mA