Operating Manual

 

 

13

 

HV Tester 25 kV

 

4.2.2  Ending testing 

Once testing is complete, turn the voltage down and switch the 
equipment off ("HV off" Figure 4 p. 11 [7]). 
When the test time expires, the high voltage is switched off 
automatically by the timer and the discharge device is activated. The 
discharge process of the test object can be followed on the measuring 
instrument. 

ATTENTION:

 

After four discharge processes at a maximum, a 
break of about 30 minutes shall be taken. 

Once the displayed high-voltage reading has dropped to 0, the test 
object can be grounded and the HV Tester disconnected. 
Finally ground/short-circuit the test object yourself. 

WARNING:

 

The high-voltage connector must not be plugged in / 
unplugged when live. 

 

In an emergency, the high voltage must be switched off by a second 
operator pressing the red "HV off" button. 

4.2.3  Safety measures 

The set must only be operated by electricians in accordance with DIN 
VDE 1005.  It must only be operated in areas, which have been secured 
and/or cordoned off and marked in accordance with DIN VDE 0104 and 
DIN VDE 0105. 
In an emergency, the high voltage must be switched off and grounded 
by a second operator pressing the red "HV off" button. 

 

N.B.:

 

Never put equipment with moisture condensation into 
operation. 

 
Please also follow the safety instructions in chapter 1. 
Reliable grounding of the HV Tester is always necessary in addition to 
adequate protection against electric shock. 

 

CAUTION:

 

Care must be taken during testing that the far end is 
also reliably protected against electric shock. 

 

Be aware that residual charges may still be present after discharge in 
the case of capacitive tests. 

 

WARNING:

 

Parallel cables may also still be charged after testing. 

Summary of Contents for 128311841

Page 1: ...HV Tester 25 kV 128311841 Operating Manual...

Page 2: ......

Page 3: ...304 207342 E uksales megger com Dr Herbert Iann Str 6 D 96148 Baunach T 49 9544 68 0 F 49 9544 22 73 E sales sebakmt com Hagenuk KMT Kabelmesstechnik GmbH Megger USA R deraue 41 D 01471 Radeburg Dresd...

Page 4: ...he date of delivery Each component supplied by Megger within the context of warranty will also be covered by this warranty for the remaining period of time but for 90 days at least Each measure to rem...

Page 5: ...Function 4 2 4 Specifications 5 3 PREPARATION FOR USE 7 3 1 Operating requirements 7 3 2 Power supply 7 3 2 1 Internal rechargeable battery 7 3 2 2 Mains 8 3 2 3 External battery 8 3 2 4 Maintenance p...

Page 6: ...Operating Manual II HV Tester 25 kV Table of Figures Figure 1 HV Tester 25 kV 4 Figure 2 HV Tester 25 kV 9 Figure 3 Example for connecting HV Tester 25 kV 10 Figure 4 Front of the HV Tester 25 kV 11...

Page 7: ...the work processes involved however there may be parts of the system and its peripherals which cannot be given optimum protection without an unreasonable reduction in function and usability The follo...

Page 8: ...g personal protection work safety and technical safety are indicated as follows WARNING Warning indicates work and operating procedures which must be complied with in full to exclude the possibility o...

Page 9: ...cable black 00006 HV connecting cable shielded incl clamp 00007 User manual Service pack 00008 Packing Table 1 Scope of supply 2 1 2 Use of the set The HV Tester 25 kV is used for electrical testing...

Page 10: ...e testing time Figure 1 HV Tester 25 kV 2 3 Function Before the set can be used the HV Tester 25 kV has to be grounded properly When the high voltage adjuster is set to zero and the timer works the te...

Page 11: ...arity infinitely variable Output current 1 5 mA Short circuit current 1 6 mA 0 1 mA Voltage measuring range 0 30 kV Current measuring range 0 0 2 mA and 0 2 mA Discharge energy 3000 J max Operating ti...

Page 12: ...Operating Manual 6 HV Tester 25 kV...

Page 13: ...ld it must be placed outside the cable trench and protected against dirt and moisture The HV Tester should be set up inside the cordon at a distance of approx 3 m from the high voltage preferably at o...

Page 14: ...urned off allowing recharging floating operation of the internal battery CAUTION Take care of the voltage selector switch 1 p 9 3 2 3 External battery The external DC voltage must be in the 11 15 V ra...

Page 15: ...The connecting cable is in the front of the carrying case 1 2 3 7 6 5 4 1 Voltage selector 2 Power supply 3 Fuse 1 25 A slow for 115 V and 230 V 4 Connector for external battery 5 Station ground 6 HV...

Page 16: ...ground terminal 5 of the HV Tester 25 kV 3 In the case of mains operation the ground safety circuit checks whether the protective ground protective conductor terminal 7 and station ground have the sa...

Page 17: ...for the high voltage with forced zero position 4 Unit on lamp Lights up white when the unit is switched on with the mains switch 8 5 Ground terminal lamp Lights up yellow when the HV Tester is ground...

Page 18: ...forced zero position Tip If you want to select testing times shorter than 5 min turn the rotary knob of the timer first beyond the position 5 and then to the desired time The red illuminated HV off 7...

Page 19: ...tage must be switched off by a second operator pressing the red HV off button 4 2 3 Safety measures The set must only be operated by electricians in accordance with DIN VDE 1005 It must only be operat...

Page 20: ...Operating Manual 14 HV Tester 25 kV...

Page 21: ...s lamps and tools are included in the service kit The HV Tester 25 kV is test equipment and as such must be handled and looked after with care Moisture external soiling direct sunlight and ambient tem...

Page 22: ...Operating Manual 16 HV Tester 25 kV...

Page 23: ...ie z me nor da ka iztr d jumu uz kura t atrodas nedr kst izmest kop ar parastiem m jsaimniec bas atkritumiem T k tas ir izstr d jums ko cits citam p rdod un lieto tikai uz mumi tad to nedr kst ar izme...

Reviews: