7
Inlet air temperature shall not exceed 55°C.
The Meech Cabinet Cooler has the following IECEx certification:
Ex h IIC T4 Gb Ta -10°C to +55°C
All other parts of the Cabinet Cooler System including the Solenoid Valve and
Thermostat must be installed outside the hazardous area.
The cold fraction adjustment valve must not be altered and remain at 2.5 turns
open.
Ambient operating temperature must not exceed 55°C
Ambient operating temperature can not drop lower than -10°C
3. Maintenance
The Meech Cabinet Cooler has no moving parts. Clean compressed air moving
through the Cabinet Cooler will not cause wear on any of the components.
Occasionally, dirt, water or oil may enter the cooler from the compressed air supply.
This could hinder the performance. If this happens simply take the unit apart, clean
the parts with soapy water, allow drying time and then reassemble.
When reassembling ensure you tighten all the components. If the parts are not
tightened correctly, the coolers performance may be affected. Also, please ensure the
generator is fitted. At the same time the element in the air filter should be changed.