13
6. Installation
The Meech Cabinet Cooler is suitable for category 1 (zone 1) T4 applications where
ATEX and/or IECEx certification is required.
All other parts of the Cabinet Cooler System including the Solenoid Valve and
Thermostat must be installed outside the hazardous area.
The drawing below shows the recommended way to fit Meech EX Cabinet Cooler.
To fit the Cabinet Cooler follow the steps below:
A. Drill Hole
Drill 1.02” (26 mm) hole in the position you would like to fit the Cabinet Cooler.
Please be aware that 200mm of the Cabinet Cooler will extend from the outside of
the enclosure so allow clearance.