15
D. Fit Cabinet Cooler in place
From outside the enclosure, place the cold end of the Cabinet Cooler into the drilled
hole.
E. Re-fit bulk head nut and washer
Once this is done tighten bulk head nut & washer until the Cabinet Cooler is secure.
F. Connect cold air ducting to the end.
It’s recommended that the cold air ducting is directed from the cabinet cooler to the
bottom of the enclosure. This will allow for increased cooling throughout the cabinet/
panel. This will also avoid any excess water vapour in the compressed air being blown
over components.
If the air is clean and dry the cold air ducting can be directed to particularly hot areas
of the enclosure. Alternatively you can drill holes in the cold air ducting and allow air to
be distributed to several areas. If you choose this method you will need to plug the end
of the cold air ducting and ensure the holes drilled into the tube are equal to the hole at
the end.
Where necessary please fit appropriate filters.
G. Connect air supply
The Cabinet Cooler has a ¼” bsp female air inlet. Standard pneumatic push-fit
compressed air fittings can be used on the Cabinet Cooler.
Please refer to section 5 when deciding on pipe sizes.