Low Oil Pressure Stop
High water temperature stop
Oil pressure sensor Open
Water temperature sensor Open
Start Failure
Stop Failure
Low Water level stop
Low Water level stop
High Oil temperature stop
RPM signal lost alarm
Over speed stop
Under speed stop
Low Fuel Level warning
Low Battery voltage warning
5. Parameters
Options
Parameters
Working voltage
DC8V----36V Continuous
Power consumption
Standby
:
24V
:
MAX 1W
Working
:
24V
:
MAX 3W
AC Voltage Input
1P2W 30VAC-276VAC (ph-N)
Rotate speed sensor
Frequency
30-9999Hz
MAX Accumulating Time
99999.9Hours
(
Min Store time:6min
)
Fuel Relay Output
Max 5 Amp DC+VE Supply voltage
Start Relay Output
Max 5 Amp DC+VE Supply voltage
AUX. OUTPUT 1
Max 2.5 Amp DC+VE Supply voltage
AUX. OUTPUT 2
Max 2.5 Amp DC+VE Supply voltage
Excitation output
Max 1AMP DC+VE supply voltage
Switch value input
Available if connecting with Battery -
Working condition
-25-65
℃
Storage condition
-40-85
℃
Protection Level
IP54
:
when waterproof rubber gasket is added
between controller and its panel
Insulation strength
Apply AC1.5kV voltage between high voltage terminal
and low voltage terminal; The leakage current is not
more than 3mA within 1min.
Overall dimension
78mm*78mm*55mm
Panel cutout
67mm*67mm
Weight
0.3Kg