DC20D MK2 GENSET CONTROLLER USER MANUAL
18
11. Parameters setting
Enter the edition page
Please set the parameters according to below steps:
1
)
In the stop mode, please
and
simultaneously, then loose, Then system
comes into menu setting.
2
)
Press
to shift up the parameters, press
to shift down the parameters,
press
to get into parameter changing page.
3
)
Press
to add number, press
to reduce number, press
cancel.
The value can be increased or decreased continuously when pressing the button
continuously. Press
to confirm the value modification.
4
)
Under display mode
,
press
to exit and save data.
Note: the data can not be saved if the user didn’t press STOP to confirm
the setting.
Parameter setting
No
Parameter
Range
(default)
Notes
0
CT rate
5-6000A/5A(
500A/5A
)
Used for setting genset CT primary
current, secondary rated current 5A.
1
Flywheel
teeth
0-300
(0)
If the setting is 0, (RPM sensor
Disabled), then RPM is resulted by Hz.
2
AUX. INPUT
1
(Functional
of PIN 8)
0- Disable.
1- Emergency stop.
2- Remote start switch.
3- Low oil pressure
alarm switch.
4- High Coolant
temperature alarm
switch.
5- High oil temperature
alarm switch.
6- Low fuel level warning
switch.
7- Low water level alarm
switch.
Choose the programmable input 1,
only for switch value input
3
AUX. INPUT
2
(Functional
of PIN 15)
0- Disable.
1- Emergency stop.
2- Remote start switch.
3- Low oil pressure
alarm switch.
4- High Coolant
temperature alarm
switch.
5- High oil temperature
alarm switch.
6- Low fuel level warning
switch.
Choose programmable input 2, switch
value input or sensor simulation value
input are available; if the sensors of
users are not in the list, please self-
define the sensor’s resistance by
connecting with PC.