DC20D MK2 GENSET CONTROLLER USER MANUAL
21
frequency, under voltage, charge
failure are all invalid during this time
except for emergency stop ,over
speed and emergency stop.
22
Idle time
0~240s
(5s)
Idle running time when crank
successfully and before engine stop.
23
Cooling time
0~999s
(30s)
After unloading, the time of cooling
down by radiator before stop. during
the delay, if the remote start signal is
valid, then genset will come into rated
running.
24
Fail to stop
10~60s
(60s)
If the RPM, frequency and oil pressure
is 0 during the stop failure time, then
the stop failure time is no needed.
25
Emergency
delay
0-10s
(1s
)
Emergency, over speed and over
frequency alarm delay.
26
Normal alarm
delay
2-20s
(5s
)
The alarm delay except for
Emergency, over speed and over
frequency alarm.
27
Over current
【
inverse tim
e
】
0.1-36.0
(36.0)
This option will not take effect until the
[D-Over phase current delay] is set to
0. The overcurrent delay is inverse
time, and the formula is T=t/((IA/IT) -
1)^2.
28
Oil pressure
delay
0-3s
(1s)
When the crank condition contains oil
pressure, if the oil pressure is higher
than the preset value and continue for
few seconds, then it is regarded as
crank success.
29
Choke close
delay
0~999s
(10s)
The choke close delay after crank
success.
30
Gens AC
system
0- 2 Poles
1- 4 Poles
2- 6 Poles
3- 8 Poles
When the flywheel teeth is set as 0,the
RPM will be resulted by frequency.
Pole 2: 50Hz---3000RPM.Pole 4:
50Hz---1500RPM.Pole 6: 50Hz---
1000RPM.Pole 8: 50Hz---750RPM
31
Low oil
pressure
alarm
0.1~10.0Bar
(1.0Bar)
When the oil pressure is lower than
the alarm value and comes into low oil
pressure delay but still lower (normal
alarm delay), then low oil pressure
alarms. if the value is set as 0.1, then
the low oil pressure
alarm is disabled.
32
High coolant
temperature
alarm
50~150
℃
(95
℃
)
When the water temperature is higher
than the alarm value and comes into
high temperature delay but still higher
(normal alarm delay), then high
temperature alarms. if the value is set
as 150, then the high temperature
alarm is disabled.
33
Under battery
voltage
0~28.0V
(8.0V
)
When the battery input is lower than
the warning value and comes into