![Mebay DC20D MK2 User Manual Download Page 21](http://html1.mh-extra.com/html/mebay/dc20d-mk2/dc20d-mk2_user-manual_1758466021.webp)
DC20D MK2 GENSET CONTROLLER USER MANUAL
20
when the setting value of shutdown
delay is over, then it is off.
2. Idle speed control:
used for speed
controller, there is output under idle
but no output under high speed.
3. Public alarm output:
when there is
any alarm output, alarm locks till
revert back.
4. Preheat:
preheat output before
start.
5. Close generator;
6. Choke control:
choke will be
started after crank success and off
after delay.
8
AUX.
OUTPUT
2
(Functional
of PIN 6)
0-6
(4. Preheat )
9
Manual crank
times
1-30
(1 time)
Crank times under mode and test
mode.
10
Auto start
crank times
1-30
(3 times)
Crank times under auto mode.
11
Auto mode
E.T.S. hold
times
1-3
(2 times)
The max E.T.S. hold on power shall be
canceled once stop success under
auto mode . The output interval time is
" Fail to stop ".
12
Crank
disconnect
0.
RPM
1.
Hz
2. RPM/Frequency
3.
RPM/Oil Pressure
4.
Frequency/Oil
Pressure
5.
RPM/Freq./Oil
Pressure
Either of the conditions can be
acceptable as crank condition. But all
of them should be meet together to
regard as stop condition.
13
RPM
disconnect
350-
999RPM
(380RPM
)
When the engine RPM is over the
condition value, then system regards it
as crank success, motor escaped.
14
Frequency
disconnect
10.0~40.0Hz
(21.0Hz)
When the gens frequency is over the
condition value, then system regards it
as crank success.
15
Oil pressure
disconnect
0.1~10.0Bar
(2.0Bar)
When the engine oil pressure is over
the condition value, then system
regards it as crank success, motor
escaped.
16
E.T.S. hold
time
0~240s
(10s)
Stop solenoid on power time.
17
Start delay
0~240s
(5s)
The time during the genset starts after
the remote start signal is valid.
18
Preheat time
0~240s
(2s)
The time needed to be preheat before
the starter on power.
19
Cranking time 3~60s
(10s)
The time when the starter is on power.
20
Crank rest
time
3~60s
(10s)
If crank failure, the waiting time before
the second test time.
21
Safety delay
1~60s
(8s)
Low oil pressure, high coolant
temperature, under speed, under