DC20D MK2 GENSET CONTROLLER USER MANUAL

12

9. Control and operation instruction

Manual Start Mode

press

and make sure it is in the stop position before starting.

Press “

” and the test file indicator is on. At this time, it is detected whether the

connection of each sensor is normal. If the sensor is open, the sensor opens an

alarm. If it is normal, the unit start process is executed in the following sequence.

automatically switch to Generator provide the power when the unit is running
normally. Press “

” The controller performs the parking process at the following

timing:

Manual start and stop process:

0RPM

Idle

Rated speed

Pre-

heat

delay

5S

Long-

est

pre-oil

supply

delay

0S

Start

Crank

delay

2S

8S

Safe

time

8S

Start

idle

time

5S

Longest

speed

increasing

time

120S

Idle

Rated speed

Pre-

heat

delay

Longest

temperature

increasing

time

10S

Longest

voltage

built/

increasing

time

120S

10S

rated

runn-

ing

Cooling
running time

30S

Stop

idle

time

5S

ETS

solen-

oid

hold

10S

Wait
Stop

30S

warming

up time

Crank

test

time

After the manual start is successful, pressing the "automatic key"

can be

converted into an automatic file. The specific working time is as follows:

0RPM

Idle

Rated speed

Pre-

heat

delay

5S

Long-

est

pre-oil

supply

delay

0S

Start

Crank

delay

2S

8S

Safe

time

8S

Start

idle

time

5S

Longest

speed

increasing

time

120S

Idle

Rated speed

Pre-

heat

delay

Longest

temperature

increasing

time

10S

Longest

voltage

built/

increasing

time

120S

10S

rated

runn-

ing

Transfer

back to

mains delay

10S

Cooling
running time

30S

Stop

idle

time

5S

ETS

solen-

oid

hold

10S

Wait
Stop

30S

warming

up time

Crank

test

time

Automatic starting mode:

press

and make sure it is in the stop position before starting.

Press “

” and the test file indicator is on. At this time, it is detected whether the

connection of each sensor is normal. If the sensor is open, the sensor opens an

alarm. If it is normal, wait for the remote start signal to be valid detected the remote

starting signal is valid. The genset will perform the starting process in the following

sequence. When the genset enters the normal rated operation, it will automatically

switch to the generator provide the power. The controller will detect the remote start

signal in real time. When the remote start signal fails to normal, the shutdown

Summary of Contents for DC20D MK2

Page 1: ...DC20D MK2 GENSET CONTROLLER USER MANUAL...

Page 2: ...t fault delay function 3 V1 2 2020 05 01 Add RS485 communication baud rate and CRC check bit setting 4 V1 3 2021 02 01 Name of unified input and output port 5 V1 4 2021 06 01 Fix known errors in wirin...

Page 3: ...ise it may cause the equipment not to work correctly Be care It is indicated that potential hazards can damage equipment without proper precautions Warning It is indicated if appropriate preventive me...

Page 4: ...mage to related equipment 5 The engine must have an overspeed protection device independent of the controller system to avoid casualties or other damage caused by engine out of control 6 After the ins...

Page 5: ...and operation instruction 12 10 Warnings and Shutdown Alarms 14 11 Parameters setting 18 12 Fault finding 23 Notes 1 All rights reserved No part of this duplication may be reproduced in any material...

Page 6: ...uter 5 Units LED tube Display LED and Fault Alarm Code Indication Totally 4 relay s output among which 2 relay output can be self configurable each relay can be set as max 6 functions It has two senso...

Page 7: ...Frequency 30 9999Hz MAX Accumulating Time 99999 9Hours Min Store time 6min Fuel Relay Output Max 5 Amp DC VE Supply voltage Start Relay Output Max 5 Amp DC VE Supply voltage AUX OUTPUT 1 Max 2 5 Amp...

Page 8: ...DC20D MK2 GENSET CONTROLLER USER MANUAL 7 6 Overall Dimension and Wiring Diagram Overall Dimension...

Page 9: ...Charging excitation output VE output Max 0 9 Amp 1 0mm2 8 Aux Input 1 Switch input Connect to the negative side of the active circuit 1 0mm2 9 Generator Voltage L Connect to generator set output L li...

Page 10: ...PUT 1 GEN CURRENT GEN VOLTS SWITCH FUSE 10 A BATTERY FUEL CRANK AUX OUTPUT 2 ALT BATTERY NEGATIVE MUST BE GROUNDED AUX INPUT 2 AUX INPUT 3 P1 P2 S1 S2 L N RS485 MPU FUSE 2A TO LOAD Note Please don t m...

Page 11: ...nected to battery positive and negative and the wire size must not be less than 2 5mm2 NOTE In case of floating charger connect charger output to battery positive and negative directly then connect ba...

Page 12: ...in Function Stop Reset Revert Can stop generator under manual auto mode Can reset shutdown alarm During stop procession pressing this key again can stop generator immediately Pressing this key can can...

Page 13: ...successful pressing the automatic key can be converted into an automatic file The specific working time is as follows 0RPM Idle Rated speed Pre heat delay 5S Long est pre oil supply delay 0S Start Cr...

Page 14: ...ssful and the motor relay is closed Note 2 Within the safety delay only respond to emergency stop over speed over frequency over voltage Speed signal lost low fuel level warning other alarms are not r...

Page 15: ...Under battery voltage warning Then start warning delay and the duration Normal alarm delay have not returned to normal the warning of Under battery voltage warning is reported Warning lights will lig...

Page 16: ...rned to normal the alarm of over speed is reported Alarm lights will light up Generators will stop displays ALA 02 on the led screen Under speed alarm When the controller detects that the engine speed...

Page 17: ...ture Switch is reported Alarm lights will light up Generators will stop displays ALA 08 on the led screen Low coolant level switch alarm When the controller detects that the AUX INPUT Low water level...

Page 18: ...Phase current over load alarm Then start alarm delay and the duration Normal alarm delay have not returned to normal the alarm of over current is reported Alarm lights will light up Generators will st...

Page 19: ...e 5 6000A 5A 500A 5A Used for setting genset CT primary current secondary rated current 5A 1 Flywheel teeth 0 300 0 If the setting is 0 RPM sensor Disabled then RPM is resulted by Hz 2 AUX INPUT 1 Fun...

Page 20: ...40 120 11 Coolant temperature sensor Datcon High 12 Coolant temperature sensor 3015238 13 Coolant temperature sensor MEBAY Mier 14 Coolant temperature sensor User defined PC to configure Choose progra...

Page 21: ...e 5 RPM Freq Oil Pressure Either of the conditions can be acceptable as crank condition But all of them should be meet together to regard as stop condition 13 RPM disconnect 350 999RPM 380RPM When the...

Page 22: ...s T t IA IT 1 2 28 Oil pressure delay 0 3s 1s When the crank condition contains oil pressure if the oil pressure is higher than the preset value and continue for few seconds then it is regarded as cra...

Page 23: ...r voltage alarms If the value is set as 500 then the alarm is disabled 37 Under voltage alarm 50 380V 100V When the voltage is lower than the value and comes into under voltage delay but still lower n...

Page 24: ...ed alarm ALA 14 Coolant temperature sensor disconnected alarm ALA 03 Under speed alarm ALA 15 Over frequency alarm ALA 04 Low oil pressure alarm sensor ALA 16 Under frequency alarm ALA 05 Low oil pres...

Page 25: ...s normal Shutdown Alarm in running Check related switch and its connections according to the information on LED Check AUX INPUT Fail to start Check fuel return circuit and wiring Check start battery C...