Technical Manual Temperature Controller
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
20
4.3 Alarm/Messages
The following settings are available at the ETS-Software:
Figure 6: Alarm/Messages
The chart shows the dynamic range of the alarm and messages:
ETS-text
Dynamic range
[default value]
comment
Alarm
not active
active
Activation of the alarm function
Frostalarm if value <
3°C-10°C
[7°C]
Dynamic range of the frostalarm
Adjustment possible if alarm is activated
Heatalarm if value >
25°C-40°C
[35°C]
Dynamic range of the heatalarm
Adjustment possible if alarm is activated
Messages
not active
active
Activation of the message function
Message if value >
18°C-40°C
[26°C]
Dynamic range of the upper message
Adjustment possible if messages are
activated
Message if value <
1°C-25°C
[13°C]
Dynamic range of the lower message
Adjustment possible if messages are
activated
Table 8: Parameter Alarm/Messages