4 Reference ETS-Parameter
4.1 General Settings
The following settings are available at the ETS-Software:
Figure 4: General settings
The chart shows the dynamic range of the general settings:
ETS-text
Dynamic range
[default value]
comment
Startup delaytime
0-60s
[0]
Time between an upload and the
functional start of the device
Setpoint frost protection
for all channels
3°C-10°C
[7°C]
Setting of the setpoint for the operating
mode frost protection
Setpoint heat protection
for all channels
25°C-40°C
[35°C]
Setting of the setpoint for the operating
mode heat protection
Flow temperature
15°C-60°C
[35°C]
Setting of the flow temperature limit
Table 3: General settings
The parameter startup timeout adjusts the time between an upload and the functional start of the
device. The used hardware reacts only after expiration of the adjusted time. All input commands
before the startup timeout expire.
Additional the setpoints for the operating modes frost- and heat-protection can be set in this menu.
These setpoints are valid for all channels. Furthermore a flow temperature limit can be set, which is
kept in the channel with activated flow temperature limit.