Technical Manual
LED-Indicator
SCN-LED55.01/SCN-GLED1x.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
23
23
4.4.2 Settings logic A-H
The object type for the logic output can be set for each logic:
ETS-text
Dynamic range
[default value]
comment
Setting Logic A-H
▪
disabled
▪
AND
▪
OR
disabled:
disables the logic module
AND:
The inputs are connected by the
logical function AND
OR:
The inputs are connected by the
logical function OR
Object type for logic
output
▪
Switch
▪
Scene
▪
Value
The “Object type for logic output” defines
the DPT of the logic function
Table 13: Settings logic
Depending on the selected logical object the additional settings are displayed.
The possible settings for a switching output can be seen below:
ETS-text
Dynamic range
[default value]
comment
Object type for logic output
Switch
Chosen logic output: Switch (1 Bit)
Send condition
▪
not automatic
▪
Change of input
▪
Change of output
Setting when the value of the output is
sent.
not automatic
: no send, only request
Change of input:
Sending at every
change of any input object
Change of output:
Sending only at
change of the output
Invert output
▪
no
▪
yes
Reverses the output at activation (0
→
1,
1
→
0)
Table 14: Settings logic output switch
The following table
shows the object for the logic output, when this is set as “Switch”:
Number
Name
Length Usage
52
Output switching
1 Bit
Output of the logic
Table 15: Logic output switching
The following settings are available for a scene output:
ETS-text
Dynamic range
[default value]
comment
Object type for logic output
Scene
Chosen logic output: Scene (1 Byte)
Scene Number
1-64
[2]
Setting which scene is called when
completing the logic function
Table 16: Logic settings - scene