8-AIR INLETS
Technical Dept. - All rights reserved - Reproduction prohibited
VENTILATION CONNECTION COMFORT AIR BASIC
Combustion air
The combustion air inlet “C” Ø
150
provided on the Plasma closed fireplace must be connected to the exterior of the cladding by a pipe
with 150 mm diameter and a maximum length of 3 metres.
Smoke outlet
Smoke outlet “D” must be connected by a smoke fitting to a suitable flue.
Convection air
Set up a low air intake grid “R” of at least 400 sq cm net and a high outlet “S” of at least 520 sq cm net, to decompress the hood.
Heating air
With forced ventilation open the two front knockout holes, connect two pipes with a diameter of 100 mm and connect them to two outlets
for the release of hot air “P”.
Control unit
Position control unit “Q” in a cold area to avoid overheating the electronics.