3-FLUE
Technical Dept. - All rights reserved - Reproduction prohibited
EXAMPLES OF CORRECT INSTALLATION
1.
Installation of Ø200mm flue with hole for the passage
of the pipe increased by:
minimum 100mm around the pipe if next to non
flammable parts such as cement, brick, etc.; or
minimum 400mm around the pipe (or as required by data
tags) if next to flammable parts such as wood etc.
In both cases, install suitable insulation between the flue
and the ceiling.
Always check and respect the data tags on the flue,
in particular the minimum safety distances from
combustible materials.
The previous rules also apply for holes made in walls.
2.
Old flue, minimum pipe Ø200mm with the inclusion of
an external access door for chimney cleaning.
3.
External flue made of insulated stainless steel pipes,
i.e. with double walls minimum Ø200mm: all securely
mounted on the wall. With windproof chimneypot.
NOTE: with closed fireplaces maintain the safety distance
indications with the included insulation indications.
U = insulation
s = inspection access panel
P = air inlet
FIGURE 11