42
IM709
START-UP
A.
Does the unit start & perform per sequence of operation as stated in IM Bulletin?
Yes
No
B.
Does the fan rotate in the right direction?
Yes
No
C.
Condenser inlet water temperature
Deg. F _____
D.
Condenser outlet water temperature
Deg. F. _____
E.
Number of Compressors Operating
Deg. F. _____
F.
Return air temperature
Deg. F. _____
G.
Mixed air temperature
Deg. F. _____
H.
Supply air temperature
Deg. F. _____
I.
Compressor Readings:
J.
Electrical Heat Readings (When installed):
FLA amps
(nameplate)
Reading
Compressor
#1
Compressor
#2
Compressor
#3
Compressor
#4
Compressor
#5
Compressor
#6
Suction Pressure, psig
Discharge Pressure, psig
Superheat Setting @ TXV
Bulb, Deg. F
Compressor RLA (name
plate)
Current, Line L1, amps
Current, Line L2, amps
Current, Line L3, amps
Reading
68KW Heat, 230v or 208v Only
@ Contactor M11
@ Contactor M12
@ Contactor M15
@ Contactor M16
Current, Line Ll, amps
Current, Line L2, amps
Current, Line L3, amps
Summary of Contents for SWT C Series
Page 23: ...IM709 23 Typical Wiring Schematics Figure 19 Power Schematic...
Page 24: ...24 IM709 Figure 20 Input Schematic Discharge Air Control DAC...
Page 25: ...IM709 25 Figure 21 Input Schematic Zone or Space Comfort Control SCC...
Page 26: ...26 IM709 Figure 22 Output Schematic Actuator Control...
Page 27: ...IM709 27 Figure 23 Output Schematic Auxiliary Fan Start Stop Control...
Page 28: ...28 IM709 Figure 24 Output Schematic Actuator Control...
Page 29: ...IM709 29 Figure 25 Output Schematic Compressor Control 4 Compressors 4 5 or 6 Stage...
Page 44: ...13600 Industrial Park Boulevard Minneapolis MN 55441 USA 763 553 5330...