IM709
5
Disassembly of Sections
If units are ordered for modular construction, they may be
easily disassembled into three sections. The figures below
illustrate the main cooling/heating, filter/waterside econo-
mizer, and fan sections. The thick lines in the figures show
where the sections are disassembled. The section are secured
by connection plates and screws. The following information
describes the location of the connecting points.
Fan section — base sections disassembly
The fan section sits on the base sections and is secured with
four steel plates. Each plate has two screws in the base sec-
tions and two screws in the fan section. Two of the plates are
shown in Figure 3. The connection plates are also the rigging
plates for the fan section only.
They must not be used for rig-
ging the entire unit.
Main cooling/heating — filter/waterside economizer
sections disassembly
The following information is for units ordered for modular
construction (code 32=1).
Note:
The disassembly of units
not ordered for modular construction (code 32=Y) will
require field modification. Units not ordered for modular
construction do not have victaulic couplings on the water
pipes and the various control sensors are mounted in the unit.
●
Two steel plates the height of the sections connect the
main cooling/heating and the filter/waterside econo-
mizer sections. The plates are secured with multiple
screws on the right and left side of the base sections.
The connection plate and screws are illustrated in Sect
A-A.
●
The filter/waterside economizer section overlaps the
main cooling/heating sections along the bottom and top
adjoining rails. Multiple screws connect the two sec-
tions along these bottom and top overlaps.
●
Victaulic couplings connect the water pipes between the
filter/waterside and main cooling/heating sections. Each
victaulic coupling is secured with two bolts
●
.The condensate drain pipe between the two sections is
connected by a flexible PVC tube with pipe clamps.
Fan
Outlets
FI
LTER SECTI
ON
EVAPORATOR
HEATER
ELECT
R
IC
AL PANEL
ECONOMI
Z
ER
A
A
Fan
Section
Main Cooling/
Heating Section
Filter/Waterside
Economizer
Section
Condenser
Compressor
Connection Plates
(2)
Figure 2
Figure 3
(1) Unit sizes 018, 023 and 028 have a single fan.
(2) Connection Plates are also the Rigging Plates for the Fan Section only.
ASD
(Optional)
Summary of Contents for SWT C Series
Page 23: ...IM709 23 Typical Wiring Schematics Figure 19 Power Schematic...
Page 24: ...24 IM709 Figure 20 Input Schematic Discharge Air Control DAC...
Page 25: ...IM709 25 Figure 21 Input Schematic Zone or Space Comfort Control SCC...
Page 26: ...26 IM709 Figure 22 Output Schematic Actuator Control...
Page 27: ...IM709 27 Figure 23 Output Schematic Auxiliary Fan Start Stop Control...
Page 28: ...28 IM709 Figure 24 Output Schematic Actuator Control...
Page 29: ...IM709 29 Figure 25 Output Schematic Compressor Control 4 Compressors 4 5 or 6 Stage...
Page 44: ...13600 Industrial Park Boulevard Minneapolis MN 55441 USA 763 553 5330...