Final Control Settings
Figure 114. Keypad accessible menu structure (continued)
CCB1 ID= _____
[2=1]
Daily Schedule
5
6
Mon= 00:00 - 00:00
Tue= 00:00 - 00:00
Wed= 00:00 - 00:00
Thu= 00:00 - 00:00
Fri= 00:00 - 00:00
Sat= 00:00 - 00:00
Sun= 00:00 - 00:00
Hol= 00:00 - 00:00
One Event Schedule
Beg= mmm dd@hh:mm
End= mmm dd@hh:mm
Optimal Start
Space Temp= xxx.x°F
Optimal Start= No
Auto Update= Yes
Htg Rate= 0.4°F/min
Htg OAT= 35°F
2nd P Sensor= None
[14=1,2 or 15=1,2 or 4]
DF CapCtrl= DuctPres
[14=1 or 2] Remote DF Cap= 25%
[14=1 or 2] RF/EF Ctrl= Tracking
[15=1,2 or 4] Rem RF/EF Cap= 25%
[15=1,2 or 4]
Eng Units= English
Passwords
Timeout= 15 min
Clear Alarm= No
Operating Hours
Fan= xxxxx hr
Mech Cool= xxxxx hr [2>0]
Comp 1= xxxxx hr [2=1]
Comp 2= xxxxx hr [2=1]
Comp 3= xxxxx hr [2=1]
Comp 4= xxxxx hr [2=1]
Heating= xxxxx hr [9>0]
Econo= xxxxx hr [7=3 or C]
Tnt Ovrd= xxxxx hr
Duct Static P Setup
[14=1 or 2]
DSP Propbd= 6.0"WC
DSP IntTime= 40 sec
DSP Period= 10 sec
Timer Settings
Service= 0 min
Recirculate= 3 min
[1=0 or 1]
Low DAT= 3 min
Max MWU= 90 min
[1=0 or 1]
Tnt Ovrd= 120 min
Start Init= 180 sec
Post Heat= 0 min
[14=1 or 2]
Time= hh:mm:ss
Day= day
Date= dd-mmm-yyyy
Fan Tracking
[14=1 or 2 & 15=1 or 2]
DF Max w/oExh= 100%
Fan Balance
[14=1 or 2 & 15=1 or 2]
Fan Balance= Off
Set Max w/o Exh= No
Set Min w/o Exh= No
Set Max w/ Exh= No
Set Min w/ Exh= No
Rem RF/EF Cap= 25%
Holiday Schedule
Hol 1=mmmdd-mmmdd
Hol 2=mmmdd-mmmdd
Hol 3=mmmdd-mmmdd
Hol 13=mmmdd-mmmdd
Hol 14=mmmdd-mmmdd
Hol 15=mmmdd-mmmdd
Hol 16=mmmdd-mmmdd
Htg Zero OAT= 0°F
Clg Rate= 0.4°F/min
Clg OAT= 85°F
Clg Zero OAT= 100°F
Unit Configuration
AHU ID= _____
Calibrate Mode= No
Space Sensor= Yes
EFT Sensor= No
ERcvry= xxxxx hr [19=1or2]
Time/Date
RF@DFMax w/oEx=95%
DF Min w/oExh= 20%
RF@DFMin w/oEx=15%
DF Max w/Exh= 100%
RF@DFMax w/Ex=60%
DF Min w/Exh= 20%
RF@DFMin w/Ex=10%
B
Economizer Setup
[7=3 or C]
Clg Propbd= 30°F
Clg IntTime= 60 sec
Clg Period= 30 sec
Compressor Setup
[2=1 & 3<8]
Lead Circuit= #1
Comp Ctrl= Cross Circ
Clg Method= Average
Cond Fan1 Spt= 0°F
Cond Fan2 Spt= 55°F
Cond Fan3 Spt= 65°F
Cond Fan4 Spt= 75°F
Cond Fan Diff= 5°F
Stage Time= 5 min
DesignFlow Setup
[8>0]
Wait Time= 30 sec
Modband= 50%
Max Step= 5.0%
Deadband= 6.0%
LH Flow= xxx.xx%
RH Flow= xxx.xx%
Bldg Static P Setup
[15=1,2 or 4]
BSP Propbd= 1.0"WC
BSP IntTime= 10 sec
BSP Period= 5 sec
Chilled Water Setup
[2=2 or A]
Clg Propbd= 30°F
Clg IntTime= 60 sec
Clg Period= 30 sec
Stage Time= 5 min
A
Sub Menus (Continued)
Exhaust Fan Setup
[15=4]
Min Exh Fan Cap= 25%
Min OA Dmpr= 5%
Min DF Cap= 10%
Min Strt Time= 120 sec
Min Stop Time= 120 sec
Feedback= 3 Wire
Feedback= 3 Wire
AI11 Reference= No
Comp 5= xxxxx hr [3=6]
Comp 6= xxxxx hr [3=6]
PRAC= No
PRAC= No
Zone Temp Setup
[1=0 or 2]
Clg IntTime= 700 sec
Period= 60 sec
Clg Propbd= 8.0°F
Spt Source= Keypad
Htg Propbd= 12.0°F
Htg IntTime= 500 sec
PRAC= No
PRAC= No
4
Dehumidification
[1=0 or 2]
Dehum Status= _____
Rel Humidity= xxx%
Dew Point= xx.x°F
Dehum Method=None
RH Setpoint= 50%
DewPoint Spt= 50°F
DewPnt Db= 2°F
RH Db= 2%
Configuration Code
Pos # 1-4= x.xxx
Pos # 5-8= x.xxx
Pos # 9-12= x.xxx
Pos # 13-16= x.xxx
Pos # 17-20= x.xxx
Pos # 21-22= x.x
CCB2 ID= _____
[2=1, & 3<8]
EHB1 ID= _____
[9=2] ERB1 ID= _____
[19=1 or 2]
GCB1 ID= ____
[3=8]
Dehumid= xxxxx hr [1=0or2]