c)
Ensure that the compressor is not expose to open air for more than the recommended time specified by
its manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor is
about to be brazed.
d) The system should be thoroughly vacuumed to 1.0 Pa ( 700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
Composition of R407C in vapour phase
is different from liquid phase.
f)
Normally, the R407C cylinder or can is being equipped with a dip pipe for liquid withdrawal. However, if
the dip pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
g) When servicing leak, the top up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made up of three different components, may have changed during the leak. Consequently, a top
up may not ensure that the R407C in the system is of original composition. This composition shift may
adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.
74
R32/R125/R134
33% / 33% / 34%
23% / 25% / 52%
Dip-pipe
Liquid
withdrawal
Invert cylinder
without dip-pipe
Summary of Contents for M5WM 007G
Page 42: ...Cooling Only Models Model MLC M5LC 020C M4LC 020B Model MLC M5LC 025C M4LC 025B 40...
Page 43: ...Heatpump Models Model MLC M5LC 007CR Model M4LC 007BR 010BR MLC M5LC 010CR 41...
Page 44: ...Model M4LC 015BR Model MLC M5LC 015CR 42...
Page 45: ...Heatpump Models Model MLC M5LC 020CR M4LC 020BR Model MLC M5LC 025CR M4LC 025BR 43...
Page 53: ...Cooling Only Models Outdoor Unit Model MLC 015C 51 Indoor Unit Model MWM 015G With Ionizer...
Page 56: ...Cooling Only Models Outdoor Unit Model MLC 015C 54 Indoor Unit Model MWM 015G With NTP...
Page 62: ...60 Cooling Only Models Outdoor Unit Oxygen Unit Model MLC 010C M5LC 010C 015C...
Page 64: ...62 Heatpump Models Outdoor Unit Model MLC 015CR Indoor Unit Model MWM 015GR With Ionizer...
Page 67: ...65 Heatpump Models Outdoor Unit Model MLC 015CR Indoor Unit Model MWM 015GR With NTP...
Page 79: ...77 Installation Diagram Installation...
Page 100: ...98 Model M5WM MWM 020G 020GR 025G 025GR...
Page 118: ...2005 McQuay International 1 800 432 1342 www mcquay com...