86
9) Final Checking
•
Ensure that steps 1 to 8 are closely followed.
•
Ensure the following, in particular :-
1) The unit is mounted solidly and rigidly in position.
2) Piping and connections are leak proof after charging.
3) Proper wiring has been done.
•
Trial run
1) Conduct a trial run after water drainage test and gas leakage test.
2) Watch out for the following :-
a) Is the electric plug firmly inserted into the socket?
b) Is there any abnormal sound from unit?
c) Is there any abnormal vibrations with regard to unit itself or pipings?
d) Is there smooth drainage of water?
•
Check that :
1) Condenser fan is running, with warm air blowing off the condensing unit.
2) Evaporator blower is running and discharging cool air.
3) Suction (Low side) pressure as per recommended.
4) The remote controller incorporate a 3 minute delay in their circuit. Thus, it requires about 3 minutes upon cut off
before the outdoor condensing unit can start up.
Diagram shows typical charging method.
Note : R407C – Fix filter dryer
R22 - Nil
R410A - Nil
CAUTION FOR R407C / R410A
Avoid prolong exposure of an opened compressor, or the internal part of refrigerant piping
to moist air. The POE oil in the compressor and piping can absorb moisture from air.
Summary of Contents for M5WM 007G
Page 42: ...Cooling Only Models Model MLC M5LC 020C M4LC 020B Model MLC M5LC 025C M4LC 025B 40...
Page 43: ...Heatpump Models Model MLC M5LC 007CR Model M4LC 007BR 010BR MLC M5LC 010CR 41...
Page 44: ...Model M4LC 015BR Model MLC M5LC 015CR 42...
Page 45: ...Heatpump Models Model MLC M5LC 020CR M4LC 020BR Model MLC M5LC 025CR M4LC 025BR 43...
Page 53: ...Cooling Only Models Outdoor Unit Model MLC 015C 51 Indoor Unit Model MWM 015G With Ionizer...
Page 56: ...Cooling Only Models Outdoor Unit Model MLC 015C 54 Indoor Unit Model MWM 015G With NTP...
Page 62: ...60 Cooling Only Models Outdoor Unit Oxygen Unit Model MLC 010C M5LC 010C 015C...
Page 64: ...62 Heatpump Models Outdoor Unit Model MLC 015CR Indoor Unit Model MWM 015GR With Ionizer...
Page 67: ...65 Heatpump Models Outdoor Unit Model MLC 015CR Indoor Unit Model MWM 015GR With NTP...
Page 79: ...77 Installation Diagram Installation...
Page 100: ...98 Model M5WM MWM 020G 020GR 025G 025GR...
Page 118: ...2005 McQuay International 1 800 432 1342 www mcquay com...