McQuay IM 685 Installation & Maintenance Manual Download Page 10

Page 10 / IM 685

Set Control System to Enable Heating

To allow start-up and check-out of the burner, the control system must be set to call for heating and
must be used to control the amount of heating. Set the control system to call for heat so OBA3
energizes Relay R20. With OBA3 closed, vary the temperature control set point to increase, maintain,
or reduce the firing rate of the burner as required for these tests. If OBA4 is closed the firing rate will
decrease. If OBA5 is closed the firing rate will increase. If neither are "made" the firing rate will remain
unchanged.

Start-up Preliminary

1. Before energizing the burner verify that the modulating air and gas valve mechanism moves freely

and is not binding, and check the linkage fasteners for tightness. This can be accomplished without
affecting any adjustments. Remove shoulder screw (12), Figure 16a, that connects the teflon bushing
to the actuator crank arm. The control rod can now be manually moved back and forth, it should
feel smooth with no binding or scraping. Always remove shoulder screw (12) and test for binding
after reinstalling the gun assembly on Models HT050-200.

2. Close the gas line cocks. Install a Keyboard Display Module, Honeywell Part No. S7800A1001, or

connect a 20K ohm/volt meter to the test jack on the flame safeguard (see Figure 7).

3. Check the burner fan wheel for binding, rubbing, or loose set screws.
4. Check power. Position switch S3 on burner control panel to AUTO. The LED marked POWER on

the flame safeguard should come on and after a 10 second "Initiate" period the burner motor should
start. Check for CCW rotation as viewed through the burner fan housing inlet. If the motor does not
start, press the reset button on the flame safeguard. If the motor still does not start, consult the
appropriate section of the "Troubleshooting Guide". Continue on to Item 5 when burner motor will
run 10 seconds after the switch is positioned to AUTO.

5. Check voltage. With burner switch S3 at AUTO, measure voltage across burner control box

terminals 2 and NB. If it is not between 114 and 126 volts, check the voltage and tapping
connections to the supplying transformer at the unit main control panel.

6. Purge the gas lines. Turn off electrical power. Remove the 

1

8

 inch pipe plug from the inlet pressure

tap of the first electric gas valve in the line. Open the gas line cocks upstream from there and bleed
the gas line of all air. Replace the 

1

8

 inch pipe plug.

7. Leak check. Using a rich soap-water mixture and a brush, check the gas lines for leaks. Correct all

leaks before starting burner. After the burner is operating and all the downstream valves are open,
leak check that portion of the gas train.

8. Connect a manometer to measure gas manifold pressure at (1), Figure 16a.  There is a 

1

8

 inch pipe

size plugged tapping in the gas line just before it enters the burner housing.

Preliminary "Dry" Run

1. Close the gas line cock. Remove the burner front cover and open the control panel door. Switches

LS1 and LS2 in the lower right hand corner of the control box should be in view and the modulating
actuator VM1 should be at the minimum rate position. Verify that the right hand switch LS1 is
being held in the 'made' position by the collar on the control rod and that the switch lever is not
bottomed out against the plastic switch housing.

2. Position the burner switch S3 to AUTO. The flame safeguard will go through a 10 second "Initiate"

period, after which the burner motor will start. The modulating gas valve actuator VM1 will drive
the air valve and gas valve to the maximum rate position. Observe the linkage for any binding, loose
fasteners, or other problems that could have resulted from shipping.

3. When the actuator reaches the maximum rate position, verify that the left hand switch LS2 is held in

the 'made' position by the collar on the control rod and that the switch lever is not bottomed out
against the plastic switch housing.

4. Position the burner switch S3 to OFF. Close the control panel door and reinstall the burner front

cover. Prepare to measure the burner air box pressure by holding a rubber manometer tube tightly
over port (4), Figure 16b. The tube must surround the hole and seal tightly against the burner
housing to measure the static pressure through the hole.

5. Position the burner switch S3 to AUTO and with the burner actuator VM1 at the maximum rate

position measure the burner air box pressure at port (4), Figure 16b. The actuator will remain at this
position for the first 20 seconds of the prepurge period. Typical static pressure readings are listed in
Table 5, Column 6. Any appreciable deviation from these values would indicate a burner air problem
that should be found before attempting to fire the burner. These problems could include linkages
disturbed during shipment, etc.

Summary of Contents for IM 685

Page 1: ...Gas Fired Furnace on McQuay Applied Rooftop Systems HT A with RM7895A Flame Safeguard Installation Maintenance Manual IM 685 Group Applied Systems Part Number 629948Y 00 Date March 1998 1998 McQuay I...

Page 2: ...nty failure state the date of installation of the unit and the date of failure along with an explanation of the malfunctions and the description of the replacement parts required Parts are warranted f...

Page 3: ...ssembly and requires no additional chimney flue pipe Breidert cap draft inducer etc Factory Mounting This burner and gas train has been installed and wired at the factory See Gas Piping Also note that...

Page 4: ...the outside of the tube See Figure 1 Also apply a bead of high temperature silicone to seal both sides to the bottom of the flue box wrapper being careful not to obstruct the square drain holes in eac...

Page 5: ...e burner is shown in Table 5 under Column 13 thru 15 Gas piping must be sized to provide the minimum required pressure at the burner when the burner is operating at maximum input Consult the appropria...

Page 6: ...20 92 190 350 730 1100 2100 3300 5900 12000 30 73 152 285 590 890 1650 2700 4700 9700 40 63 130 245 500 760 1450 2300 4100 8300 50 56 115 215 440 670 1270 2000 3600 7400 60 50 105 195 400 610 1150 18...

Page 7: ...s to avoid interference with swinging of doors etc Through the Curb Piping Models 020 thru 140 1 Remove bottom access panel See Figure 3c 2 Remove knockout and make an opening through bottom deck dire...

Page 8: ...re only a connection to the supply gas line The manual shutoff valve is located within the burner vestibule If local codes require a manual shutoff valve that is accessible from outside the unit that...

Page 9: ...tc 2 Review the equipment and service literature and become familiar with the location and purpose of the burner controls Determine where the gas and power can be turned off at the unit and upstream o...

Page 10: ...electric gas valve in the line Open the gas line cocks upstream from there and bleed the gas line of all air Replace the 1 8 inch pipe plug 7 Leak check Using a rich soap water mixture and a brush ch...

Page 11: ...until after a period of main flame operation has further purged the gas lines before trying to adjust out something that may actually be caused by air in the lines Modulate Firing Rates Set the tempe...

Page 12: ...he flame safeguard FSG Upon a call for heat the control system will close OBA3 thus energizing relay R20 When 120 volt power is furnished through the system on off switch S1 through the burner on off...

Page 13: ...flame rod FD at the completion of the 10 second trial for ignition period terminal 10 ignition transformer IT will be de energized and terminal 9 relay coil R23 and main gas valves GV4 etc will be ene...

Page 14: ...history It can be mounted to the RM7895A and will retrieve information on the six most recent faults Consult the Honeywell bulletin 65 0090 1 7800 Series Keyboard Display Module and 65 0118 1 7800 Ser...

Page 15: ...e RM7895A which are energized to indicate operation as follows POWER The RM7895A is powered PILOT The prepurge period is complete and the terminal for the start combination gas control is powered FLAM...

Page 16: ...rly careful to correctly reinsert the air tube into the grommeted hole The tube should slip into the grommet so there is little leakage but it should not bear down on it or it can cause binding on the...

Page 17: ...ure is not an option the following discussion on the High Pressure Regulator would still apply High Pressure Regulator If a high pressure regulator is included as part of the burner gas train or is in...

Page 18: ...et that connects the air and gas valves must be correctly positioned on the control rod such that the bracket will be firmly held under tension against its stop when the actuator is in the minimum rat...

Page 19: ...of 2000 feet and higher the gas burner must be derated 4 for every 1000 feet of altitude Example Model HT080 at an altitude of 3000 feet is derated 0 04 x 3 0 12 At 1000 mbh input 1000 x 0 12 120 mbh...

Page 20: ...e adjusted to the flow rate used for this procedure is too high and must be reduced by repositioning the actuator to a lower firing rate or the gas supply line pressure is too low After adjusting valv...

Page 21: ...will be diluted with outside air and lower readings will result If flue gas temperature is to be measured this must be done in the flue box not in the tube The temperature gradient within the tubes w...

Page 22: ...bulator in each tube approximately flush with the tube end locking them in place with the wedge clips on each turbulator 8 Reinstall flue box front wrap Figure 14 Models 020 thru 025 Heat Exchanger Le...

Page 23: ...Rate 2 Control Failure The limit control does not function properly to shut off the burner when the heat exchanger temperature becomes excessive In most situations a properly controlled unit will nev...

Page 24: ...condensate However suitable steps should be taken to manage the flow of the condensate produced Most condensate will be produced in the secondary tubes where flue gas will sweep it into the flue box C...

Page 25: ...eyboard display module or a DC voltmeter Twice Yearly 1 Burner Air Check burner fan wheel for dirt build up and lint Check combustion air intake louver and flue box for dirt buildup and accumulation o...

Page 26: ...als 7 and L2 on the flame safeguard stays there the Keyboard when the burner fan is running Display Module indicates Purge Hold 2 2 Burner motor runs valve a Timer TD10 is not making after 20 seconds...

Page 27: ...ressure will build up on the downstream side thus exceeding the rating of the gas train components b Undersized piping can also cause problems by delivering reduced pressure during times of maximum de...

Page 28: ...64148A 04 040 Burner Gun Assembly 1 964148A 05 050 Burner Gun Assembly 1 964148A 06 064 065 Burner Gun Assembly 1 964148A 08 079 080 Burner Gun Assembly 1 964148A 10 100 Burner Gun Assembly 1 964148A...

Page 29: ...N n i M M F C x a M R T F g e D g n i r u D e g r u p e r P e t a R x a M r e n r u B g n i t a r e p O e t a R x a M g n i r u D e g r u p e r P e t a R x a M x a M e t a R n i M e t a R 5 e t o N 5...

Page 30: ...T t n e i b m A F g e D e r u t a r e p m e T s a G e u l F t n e c r e p 2 O C M P P O C C W n I x o B n i e r u s s e r P r i A Flue Gas Flue Gas s t n e m m o C y n a e z i r a m m u S k r o w e c...

Page 31: ...IM 685 Page 31 Notes...

Page 32: ...13600 Industrial Park Boulevard P O Box 1551 Minneapolis MN 55440 USA 612 553 5330...

Reviews: