14
IM 676
Table 9, Physical data ALR080E Through 100E
PHYSICAL DATA
ALR MODEL NUMBER
080E
085E
090E
100E
BASIC DATA
Ckt.1
Ckt.2
Ckt.1
Ckt.2
Ckt.1
Ckt.2
Ckt.1
Ckt.2
Unit Capacity @ ARI Conditions (1), Tons (kW)
81.3 (285.9)
85.3 (300.0)
92.7 (326.0)
99.2 (348.8)
Number Of Refrigerant Circuits
2
2
2
2
Unit Operating Charge, R-22, Lb.
62
62
65
65
65
65
68
68
Unit Operating Charge, R-22, (kg)
(22.7)
(22.7)
(22.7)
(22.7)
(24.9)
(24.9)
(24.9)
(24.9)
Cabinet Dimensions, LxWxH, In.
229 x 83 x 59
229 x 83 x 59
229 x 83 x 59
229 x 83 x 59
Cabinet Dimensions, LxWxH, (mm)
(5817 x 2108 x 1499)
(5817 x 2108 x 1499)
(5817 x 2108 x 1499)
(5817 x 2108 x 1499)
Unit Operating Weight, Lbs. (kg)
7055 (3200)
7680 (3484)
7685 (3486)
7830 (3552)
Unit Shipping Weight, Lbs. (kg)
6685 (3032)
7310 (3316)
7315 (3318)
7535 (3418)
Add'l Weight If Copper Finned Coils, Lb. (kg)
826 (375)
826 (375)
826 (375)
826 (375)
COMPRESSORS
Type
Semi-Hermetic
Semi-Hermetic
Semi-Hermetic
Semi-Hermetic
Nominal Horsepower
25-25
25-25
25-25
30-25
30-25
30-25
30-30
30-30
Number Of Cylinders Per Compressor
4 - 4
4 - 4
4 - 4
4 - 4
6 - 4
6 - 4
6 - 4
6 - 4
Oil Charge Per Compressor, Oz.
130 - 130
130 - 130
130 - 130
140 - 130
140 - 130
140 - 130
140 - 140
140 - 140
Oil Charge Per Compressor, (g)
(3686 - 3686)
(3686 -
3686)
(3686 -
3686)
(3969 -
3686)
(3969 -
3686)
(3969 -
3686)
(3969 -
3969)
(3969 -
3969)
CAPACITY REDUCTION STEPS - PERCENT OF COMPRESSOR DISPLACEMENT
Standard Staging - Circuit #1 in Lead
Standard 6 Stages
0-13-25-38-50-75-100
0-12-24-36-48-72-100
0-19-39-48-58-79-100
0-18-36-45-54-76-100
Standard Staging - Circuit #2 in Lead
Standard 6 Stages
0-13-25-38-50-75-100
0-12-24-36-48-76-100
0-19-39-48-58-79-100
0-18-36-45-54-76-100
Optional Staging - Circuit #1 in Lead
Optional 8 Stages
0-13-25-38-50
0-12-24-36-48
0-19-39-48-58
0-18-36-45-76
-63-75-88-100
-60-76-88-100
-69-81-90-100
-68-82-91-100
Optional Staging - Circuit #2 in Lead
Optional 8 Stages
0-13-25-38-50
0-12-24-36-48
0-19-39-48-58
0-18-36-45-76
-63-75-88-100
-64-76-88-100
-69-81-90-100
-68-82-91-100
CONDENSERS - HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING
Coil Face Area,Sq. Ft.
57.8
57.8
57.8
57.8
57.8
57.8
57.8
57.8
Coil Face Area, (M
2
)
(5.4)
(5.4)
(5.4)
(5.4)
(5.4)
(5.4)
(5.4)
(5.4)
Finned Height x Finned Length, In.
40 x 208
40 x 208
40 x 208
40 x 208
40 x 208
40 x 208
40 x 208
40 x 208
Finned Height x Finned Length, (mm)
(1016 x 5283)
(1016 x
5283)
(1016 x
5283)
(1016 x
5283)
(1016 x
5283)
(1016 x
5283)
(1016 x
5283)
(1016 x
5283)
Fins Per Inch x Rows Deep
16 x 3
16 x 3
16 x 3
16 x 3
16 x 3
16 x 3
16 x 3
16 x 3
Maximum Relief Valve Pressure Setting, psig (kPa)
450 (3103)
450 (3103)
450 (3103)
450 (3103)
450 (3103)
450 (3103)
450 (3103)
450 (3103)
CONDENSER FANS - DIRECT DRIVE PROPELLER TYPE
Number Of Fans - Fan Diameter, In. (mm)
10 - 26 (660)
10 - 26 (660)
10 - 26 (660)
10 - 26 (660)
Number Of Motors - HP (kW)
10 - 1.0 (.7)
10 - 1.0 (.7)
10 - 1.0 (.7)
10 - 1.0 (.7)
Fan And Motor RPM, 60/50Hz
1100/915
1100/915
1100/915
1100/915
60 Hz Fan Tip Speed, FPM
7760
7760
7760
7760
60 Hz Total Unit Airflow, CFM
58000
58000
58000
58000
DIRECT EXPANSION EVAPORATOR - BAFFLED SHELL AND THRU-TUBE
Diameter, in. - Length, Ft.
12 - 08
14 - 10
14 - 10
14 - 10
Diameter, (mm) - Length, (mm)
(305 - 2439)
(356 - 3048)
(356 - 3048)
(356 - 3048)
Water Volume, Gallons, (L)
24.30 (92)
36.10 (136.6)
36.10 (136.6)
36.10 (136.6)
Maximum Water Pressure, psig (kPa)
175 (1207)
175 (1207)
175 (1207)
175 (1207)
Maximum Refrigerant Working Pressure, psig (kPa)
225 (1552)
225 (1552)
225 (1552)
225 (1552)
Water Inlet / Outlet Victaulic Connections, In. (mm)
5 (127)
6 (152.4)
6 (152.4)
6 (152.4)
Drain - NPT int, In. (mm)
.375 (9.5)
.375 (9.5)
.375 (9.5)
.375 (9.5)
Vent - NPT int, In. (mm)
.375 (9.5)
.375 (9.5)
.375 (9.5)
.375 (9.5)
NOTE:
1. Nominal capacity based on 95F ambient air and 54F/44F water range.