The electrical power must be provided with
protection devices (circuit breaker or fuse)
with double pole separation system (phase +
neutral) with minimum contact gap of 3mm.
INTERCONNECTION
CABLE
TERMINAL
STRIP
INDOOR
UNIT
TERMINAL STRIP
OUTDOOR UNIT
N
L
COMP
A
4WV
OF
N
L
COMP
A
4WV
OF
N
L
Model
40DR
50DR
Voltage range
380V – 415V/3Ph/50Hz +N +
!
Power Supply Cable size
mm
2
4.0
4.0
Number of conductors
5
5
Interconnection Cable size
mm
2
1.5
1.5
Number of conductors
7
7
Recommended fuse
A
15
20
IMPORTANT:
These values are for information only, they should be checked and selected to comply with the local and/or
national codes and regulations. They are also subjected to the type of installation and size of
conductors used.
N
L
COMP
A
4WV
OF
N
L
COMP
A
4WV
OF
S
N
T
R
TERMINAL
STRIP
INDOOR
UNIT
INTERCONNECTION
CABLE
The electrical power must be provided with
protection devices (circuit breaker or fuse) with
pole separation system, minimum contact gap
of 3mm.
TERMINAL
STRIP
OUTDOOR
UNIT
POWER SUPPLY
CABLE
IMPORTANT:
These values are for information only, they should be checked and selected to comply with the local and/or
national codes and regulations. They are also subjected to the type of installation and size of
conductors used.
Ensure that the colors of wires on the outdoor unit and the terminal markings are the same as the indoor unit
respectively.
Caution
CE30DR
CE40/50DR
POWER SUPPLY
CABLE
OUTDOOR COIL SENSOR
CED1099 (10~14/E)
2/1/01, 3:48 PM
11