1-2
English
•
Unit subjects to floor installation must be placed on a concrete slab. The slab must have thickness of 100mm and 50mm
wider and longer than the footprint of the unit (Figure 8). Place the concrete slab a distant from building to prevent
vibration and noise.
•
In the case of heatpump operation with an outdoor temperature below 0°C, the unit must be installed at least 300mm above
ground level. This is necessary to prevent ice from accumulating on the frame and to permit proper operation in the event
of heavy snowfalls.
•
The unit must be leveled on both axes. (Tolerance is less than 2mm per meter.)
WATER PIPING AND FITTING
•
All water pipe must be adequately insulated to prevent capacity losses and condensation.
•
Install a 40 to 60-mesh strainer to ensure good water quality.
•
Water pipes recommended are black steel pipe and copper pipe.
•
During installation, the piping of the unit should be clamped before rotating the installation pipe to reduce the moment
induce on the piping.
•
Users are recommended to install the pipes and accessories as shown in Figure 10.
•
An air vent must be installed at the highest position, while a drainage plug at the lowest position of the water circuit. After
the leak test (0.6MPa), open the air vent to release any air trapped in the water circuit.
•
Run the clean water through the water inlet and operate the pump to drain out the dirty water. Clean the strainer after
running the pump for 30 minutes.
•
Fill up the water circuit after connecting the pipes and equipment. Check water leakage at all connections and joints. Do
not start the unit when the system is leaking.
•
To optimize the capacity of the system, ensure that the system is free of air bubbles. The air trapped in the system would
make the system unbalanced.
Table A-1 : R410A - Heatpump Unit
Model
5ACV30CR
5ACV55CR
5ACV75CR
Operating Weight
kg
125.5
173.3
200
Refrigerant charge R410A
kg
2.1
4.1
4.8
Compressor
1 Inverter Compressors
Control system
LCD Electronic Control
Hydronic circuit
Pump
Horizontal Multistage End-Suction
Available pressure (Cooling/Heating)
kPa
77/70
125/114
220/201
Water inlet connection (BSPT)
inches
1
1
1
Water outlet connection (BSPT)
inches
1
1
1
Drain tap coupling (BSPT)
inches
1/2
1/2
1/2
Closed expansion tank water volume
litre
5
5
5
O/D Fan
Air flow (high speed)
m3/hr
3738
3738
6450
PHYSICAL DATA
Summary of Contents for 5ACV 30 CR
Page 2: ......
Page 7: ...v ELECTRICAL WIRING DIAGRAM PART NO 50 13 9 026086 Figure 1 5ACV 30 CR...
Page 8: ...vi PART NO 50 13 9 026087 5ACV 55 CR Figure 2...
Page 9: ...vii PART NO 50 13 4 083602 5ACV 75 CR Figure 3...
Page 12: ...x UNIT INSTALLATION 5ACV 30 CR Figure 9a Figure 9b 5ACV 55 CR 75 CR...
Page 58: ...6 1 3 4 R410A 4 5 6 6 7 7 i v x 1 1 2 2 3 3 3 11 5 6 7...
Page 64: ...6 7 BK H C 14 1 2 3 4 pa...
Page 73: ...MEMO LE M MO MITTEILUNG PROMEMORIA EL MEMOR NDUM NOT NOT NOT NOT NOT...
Page 74: ...MEMO LE M MO MITTEILUNG PROMEMORIA EL MEMOR NDUM NOT NOT NOT NOT NOT...
Page 75: ......
Page 78: ......
Page 91: ...viii 5ACV 30 CR qJA a qJA b 5ACV 55 CR 75 CR b u VO d...
Page 92: ...vii qJA qJA qJA uN U d v b uN U d uN U d uN U d uN U d b v uN U d uN U d uN U d uN U d uN U d...
Page 93: ...vi qJA oOKF oOKF e qJA oOKF oOKF e 5ACV 30 CR 5ACV 55 CR 5ACV 75 CR 5ACV 55 CR 5ACV 75 CR...
Page 94: ...v 50 13 4 083602 e r 5ACV 75 CR qJA...
Page 95: ...iv 50 13 9 026087 e r 5ACV 55 CR qJA...
Page 96: ...iii 50 13 9 026086 e r qJA 5ACV 30 CR wzU dNJ pOK jD...
Page 98: ...i 5ACV 30 CR 5ACV 55 CR U dNJ q U U d U q b q b U U d UF _ wDOD r d...
Page 99: ......