background image

Page 8 

 

10-1008-194 Rev. 2 

                            

TROUBLE SHOOTING 

 

Basic Air Conditioning Trouble Shooting Check List

 

 
1. 

Check manufacturer’s nameplate located on the unit for 

correct power supply. 

 

2. 

Turn the power to the unit on. The evaporator (Enclosure or “COLD” air) fan should come on. Is 

there airflow? 
 
 

YES, proceed to step # 3. 

 
 NO, 

possible: 

 Open 

motor 

winding 

   

 

 

 

 

Stuck fan motor  

 

 

    Obstructed 

blades 

 

 

 
3. 

Check thermostat setting? Adjust thermostat to the lowest setting. This should  turn the 

condenser fan and the compressor on. Did condenser fan and compressor come on when the thermostat 
was turned on? 
 
 

YES, proceed to step #4. 

 

 

 NO, 

possible: 

 Defective 

thermostat 

   

 
4. 

Are both fans and the compressor running? If not the unit will not cool properly. 

 
5. 

Check condenser ( Ambient or “HOT” air ) fan for airflow. Is there airflow ? 

 
 

YES, proceed to step # 6. 

 
 NO, 

possible: 

 Defective 

thermostat 

   

    Open 

motor 

winding 

   

 

 

 

 

Stuck fan motor  

    Obstructed 

blades 

 

 

 
6. 

Carefully check the compressor for operation - motor should cause slight vibration, and the outer 
case of the compressor should be warm. 

 
 

YES, wait 5 minutes, then proceed to step #7. 

 
 

NO, possible:   

Defective thermostat   

    Defective 

capacitor 

 

 

   

    Defective 

overload 

 

 

   

 

 

 

 

Defective relay   

 

Make sure the coils are clean. Then check evaporator “air in” and “air out” temperatures. If the 
temperatures are the same: 

 
 

 

 

 

Possible loss of refrigerant   

 

 

 

 

 

 

Possible bad valves in the compressor    

 
     
8. 

To check for a bad thermostat. Turn power to the unit off. Remove control box cover, place both 
thermostat wires onto one terminal (replace control box cover for safety). This will bypass the 
switch in the thermostat. Turn the power on. If both fans and the compressor come on, the 
thermostat needs to be replaced. 

Repair or Replace 

defective parts. 

Replace  part.

Repair or Replace 

defective parts. 

Repair or Replace 

defective parts. 

Repair or Replace 

defective parts. 

Summary of Contents for T15-0116-GXXX Series

Page 1: ...INSTRUCTION MANUAL FOR T15 AIR CONDITIONER McLean Thermal 11611 Business Park Blvd N Champlin MN 55316 Tel 763 323 8200 Fax 763 576 3200 www mcleanthermal com...

Page 2: ...n and packing material and request an inspection Then file a claim with the delivering carrier McLean Thermal cannot accept responsibility for freight damages however we will assist you in any way pos...

Page 3: ...ill continue to operate and the compressor will restart after it has cooled to within the thermal overload cut in temperature setting INSTALLATION Step 1 Inspect air conditioner Verify functionality b...

Page 4: ...ltage Hz Amps Phase Temp o F o C Lbs Kgs T15 0116 GXXX 115 60 3 6 1 800 131 55 27 12 3 T15 0116 GXXX 100 50 3 8 1 800 125 52 27 12 3 T15 0126 GXXX 230 60 1 5 1 900 131 55 27 12 3 T15 0126 GXXX 220 50...

Page 5: ...0 Coil Condenser 15 1001 02 15 1001 02 Coil Condenser Coated 15 1001 01 15 1001 01 Coil Evaporator 15 1001 03 15 1001 03 Compressor 10 1016 82 10 1026 101 Filter Air Reusable 10 1000 91 10 1000 91 Fil...

Page 6: ...10 1008 194 Rev 2 Page 5 T15 Wire Diagram T15 Schematic...

Page 7: ...is hermetically sealed properly lubricated at the factory and should provide years of satisfactory operating service Should the refrigerant charge be lost recharging ports access fittings on the suct...

Page 8: ...sis The inlet air filter is located behind the front cover To access filter pull ring protruding from slot in bottom of front cover The filter may now be cleaned or new filter installed Cleaning Instr...

Page 9: ...O possible Defective thermostat Open motor winding Stuck fan motor Obstructed blades 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compre...

Page 10: ...t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Under sized breaker fuse or not time del...

Page 11: ...s will assume the balance of the warranty on the part returned for warranty consideration Please be advised According to the Federal Register no person maintaining servicing repairing or disposing of...

Reviews: