Symptoms and Possible Causes:

 

 
 

 

SYMPTOM 

    POSSIBLE 

CAUSE 

 
Unit won’t cool   

 

 

* Clogged fins on coil(s) 

 

 

 

 

 

* Dirty filter 
* fans not running 

     * 

Compressor 

not 

running 

 

 

 

 

 

* Compressor runs, but has bad valves 

     * 

Loss 

of 

refrigerant 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor tries to start but won’t run 

* Low line voltage at start. Should be +/-10% rated voltage  

     * 

Compressor 

motor 

stuck 

     * 

Bad 

contactor 

     * 

Bad 

overload 

switch 

     * 

Bad 

run/start 

capacitor 

 
 
Unit blows breakers 

 

 

* Under sized breaker/fuse or not time delayed 

 

 

 

 

 

* Short in system 

 
 
Getting water in enclosure 

 

* Drain plugged 

     * 

Drain 

tube 

kinked 

 

 

 

 

 

* Enclosure not sealed (allowing humidity in) 

     * 

Mounting 

gasket 

damaged 

 

 
  
 
 

For additional technical information (i.e., amp draw, pressures, temperatures) 
contact McLean Thermal at 763-323-8200. 

 
 
 
 
 
 
 

Summary of Contents for T15-0116-GXXX Series

Page 1: ...INSTRUCTION MANUAL FOR T15 AIR CONDITIONER McLean Thermal 11611 Business Park Blvd N Champlin MN 55316 Tel 763 323 8200 Fax 763 576 3200 www mcleanthermal com...

Page 2: ...n and packing material and request an inspection Then file a claim with the delivering carrier McLean Thermal cannot accept responsibility for freight damages however we will assist you in any way pos...

Page 3: ...ill continue to operate and the compressor will restart after it has cooled to within the thermal overload cut in temperature setting INSTALLATION Step 1 Inspect air conditioner Verify functionality b...

Page 4: ...ltage Hz Amps Phase Temp o F o C Lbs Kgs T15 0116 GXXX 115 60 3 6 1 800 131 55 27 12 3 T15 0116 GXXX 100 50 3 8 1 800 125 52 27 12 3 T15 0126 GXXX 230 60 1 5 1 900 131 55 27 12 3 T15 0126 GXXX 220 50...

Page 5: ...0 Coil Condenser 15 1001 02 15 1001 02 Coil Condenser Coated 15 1001 01 15 1001 01 Coil Evaporator 15 1001 03 15 1001 03 Compressor 10 1016 82 10 1026 101 Filter Air Reusable 10 1000 91 10 1000 91 Fil...

Page 6: ...10 1008 194 Rev 2 Page 5 T15 Wire Diagram T15 Schematic...

Page 7: ...is hermetically sealed properly lubricated at the factory and should provide years of satisfactory operating service Should the refrigerant charge be lost recharging ports access fittings on the suct...

Page 8: ...sis The inlet air filter is located behind the front cover To access filter pull ring protruding from slot in bottom of front cover The filter may now be cleaned or new filter installed Cleaning Instr...

Page 9: ...O possible Defective thermostat Open motor winding Stuck fan motor Obstructed blades 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compre...

Page 10: ...t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Under sized breaker fuse or not time del...

Page 11: ...s will assume the balance of the warranty on the part returned for warranty consideration Please be advised According to the Federal Register no person maintaining servicing repairing or disposing of...

Reviews: