Digital Input Setup
The DI1 and DI2 Setup
Menus are used to program
the operation of the two
discrete inputs.
Digital Input Functionality
The digital input functionality must be configured
and a wide range of selections are made available
to the user providing the flexibility to match their
specific application. These inputs should be
configured before activating the system. First the
functionality of the digital input must be configured.
The choices are; “Off”, “Start”, “Stop”, “Start/Stop”,
“Speed 1”, “Speed 2”, “Speed 3” and “Start Inhibit”
(Start Inhibit) as defined in Table 3.
Use the “
▼
” or “
▲
” keys to highlight the desired function. Press and hold
MODE
key to save changes.
Table 3. Digital Input Functionality
OFF – Disables the discrete input
Start – When configured to Start, DI1 or DI2 will be used to Start the engine.
Stop - When configured to Stop, DI1 or DI2 will be used to Stop the engine.
Note: For safe operation in A/S mode be sure to set one DI to a setting of
“Start/Stop” or “Stop”.
Start/Stop - When configured to Start/Stop, DI1 or DI2 will be used to Start the
engine when the active state occurs and then Stop the engine when active state
goes inactive.
Speed 1 - When configured to Speed 1, DI1 or DI2 will ramp the engine to the
Speed 1 setting.
Speed 2 - When configured to Speed 2, DI1 or DI2 will ramp the engine to the
Speed 2 setting.
Speed 3 - When configured to Speed 3, DI1 or DI2 will ramp the engine to the
Speed 3 setting.
Start Inh - When configured to Start Inh (i.e., Start Inhibit), the engine will not start.
M300DP L Series Expansion I/O Module – Installation / User Manual
Copyright 2016 MBW Technologies, LLC All Rights Reserved
23
Technical Specifications
Parameter
Specification
Operating Voltage
9 to 32 VDC
Communication
J1939 CAN 2.0B
Operating Temperature
-30C to +70C (-22F to 158F)
Storage Temperature
-40C to +80C (-40F to 176F)
Reverse Polarity Protection
Yes
Salt Spray
IEC60068-2-52: 1996
0.18 Dia or #
8 screw
No Tests Performed
EMC
IEC61000 and EN55022
No Tests Performed
Degree of Protection
IP67
Dimensions
102.294mm x 53.39mm x 27.3mm
(4.053” x 2.102” x 1.075”)
System Protection
Provided externally
System Components
Part Number Description
M300DP Expansion I/O Module
/AS Add M300DP to any M150B or M150L Series product
MN10036 Manual – User M154L Yanmar T4F
MN10047 Manual – M300DP Expansion I/O Control for B Series Panels
MN10058 Manual – M300DP Expansion I/O Control for L Series Panels
MN10060 Data Sheet – M300DP Expansion I/O for L Series Panels