M300DP L Series Expansion I/O Module – Installation / User Manual
26
Copyright 2016 MBW Technologies, LLC All Rights Reserved
M300DP Main Menu – con’t
M300DP L Series Expansion I/O Module – Installation / User Manual
Copyright 2016 MBW Technologies, LLC All Rights Reserved
11
Active State
The DI1 and DI2 inputs may be set for an input device that has either a
Normally Open (N.O.) or Normally Closed (N.C.) contacts. The active
state for a N.O. switch is “Closed” (closure to ground) and the active state
of a N.C. switch is “Open”.
Use the “
▼
” or “
▲
” keys to highlight desired active state. Press and hold
MODE
key to save selection.
On Delay (s)
The On Delay parameter controls how long (0 to 60.0 seconds) the active
state is present before action is taken.
Use the “
▼
” or “
▲
” keys to adjust delay time. Press and hold
MODE
key
to save changes.
Off Delay (s)
The Off Delay parameter controls how long (0 to 60.0 seconds) the
inactive state is present before action is taken.
IO Status
IO Status is a diagnostic screen. The IO Status
display provides the Mode, the status of the two
digital inputs and the raw ADC counts for the two
analog inputs. AS provides the status of the
keyswitch: Auto position = 1, On position = 2,
Start position = 3.
An Analog input value of 0 indicates the input is shorted. A value of 1023
indicates the input is open.