6
User
interface, operation and functions
UGW X-series
User interface, operation and functions
50 of 66
These files can be transferred between the computer and the universal gateway (download/upload)
on this page. The
Edit
buttons open text windows in which you can edit the relevant files directly. No
further file transfers are required for this.
Rows with a hash # at the beginning are comments. Rows without # at the beginning are activated
settings.
Confirm the changes with
[Save]
and carry out a simple restart of the communication software.
6.4.6
BACnet > Persistent data
The properties of BACnet objects can be configured in such a way that they can be written via
BACnet and a change is saved “persistently*.” When a property value is saved persistently, it can
mean that there is an “initial” value in the configuration file and a value from persistent memory. This
dialog is used to merge these two values again through a decision by the user.
Delete persistent data:
If the persistent value is deleted, the original value from the configuration
applies.
Use persistent data for configuration:
The persistent value is written to the configuration file and
deleted from persistence as soon as the persistent value is used.
*Persistent
means that the changed value is active when the gateway is restarted (accordingly, non-persistent means that the changed
value is “forgotten” after a restart and it begins with the configured value again).