6
User
interface, operation and functions
UGW X-series
User interface, operation and functions
45 of 66
c) IP Mode = Foreign device
The gateway is set as a foreign device subscriber to the BACnet network.
IP address BBMD server:
The IP address of the BBMD which is to be used by the UGW for logging in as a foreign device.
UDP port BBMD server:
You can define the UDP port of the BBMD server as a decimal number (default value: 47808 dec.
(0xBAC0 hex.)).
Reregister interval:
Time in seconds after which the gateway must newly register with the BBMD.
B) Gateway mode: Data links = BACnet MS/TP
BACnet MS/TP is the connection for BACnet devices via the RS485 (two-wire) interface. The
necessary settings can be made here. Ask the BACnet coordinator about the settings for your
project.