2
Concepts
, functions and gateway design
UGW X-series
Concepts, functions and gateway design
13 of 66
[140 protB parameter 29]
target = 110 protA address8
Example mapping of a two-stage actual value (1 = day, 2 = night) to two binary values
Entry in file protA.txt
[M address83]
name = operating status from
protocol A
query = pe
Entry in file protB.txt
[S parameter 129]
name = operating status day to
protocol B
query = pe
[S parameter 130]
name = operating status night to
protocol B
query = pe
Entry in file dispatch.txt
# Mapping of the operating status
[110 protA address83]
threshold = 1
value = 1
target = 140 protB parameter 129
[110 protA address83]
threshold = 1
value = 0
target = 140 protB parameter 130
[110 protA address83]
threshold = 2
value = 0
target = 140 protB parameter 129
[110 protA address83]
threshold = 2
value = 1
target = 140 protB parameter 130
Example of configuring M-Bus to BACnet
File: bac1.txt
[Y local.AI 1001]
name = Slave 1 Value 1
query = pe
writecache = yes
bac_units = 95
bac_cov_increment = 0
bac_resolution = 0.1
File: mbus1.txt
[X P26 value 1]
name = Slave 1 Value 1
query = pe
File: dispatch.txt
# Slave 1 Value 1
[60 mbus P26 value 1]
target = 940 bac local.AI 1001
2.6
Technical design and operating principle
Technical design of the gateway connection:
Example:
Modbus master RTU/BACnet IP