8
WARNING
REFRIGERANT UNDER PRESSURE!
Failure to follow proper procedures may cause property
damage, personal injury or death.
NOTE: Scroll compressors should never be used
to evacuate or pump down a heat pump or air
conditioning system.
CAUTION
Prolonged operation at suction pressures less than 20 psig
for more than 5 seconds will result in overheating of the
scrolls and permanent damage to the scroll tips, drive
bearings and internal seal.
Deep Vacuum Method (Recommended)
The Deep Vacuum Method requires a vacuum pump
rated for 500 microns or less. This method is an effective
and efficient way of assuring the system is free of non-
condensable air and moisture. As an alternative, the Triple
Evacuation Method is detailed in the Service Manual for
this product model.
It is recommended to remove the Schrader Cores from the
service valves using a core-removal tool to expedite the
evacuation procedure.
1. Connect the vacuum pump, micron gauge, and
vacuum rated hoses to both service valves.
Evacuation must use both service valves to eliminate
system mechanical seals.
2. Evacuate the system to less than 500 microns.
3. Isolate the pump from the system and hold vacuum
for 10 minutes (minimum). Typically, pressure will rise
slowly during this period. If the pressure rises to less
than 1000 microns and remains steady, the system is
considered leak-free; proceed to system charging and
startup.
4. If pressure rises above 1000 microns but holds steady
below 2000 microns, non-condensable air or moisture
may remain or a small leak is present. Return to step
2: If the same result is achieved check for leaks and
repair. Repeat the evacuation procedure.
5. If pressure rises above 2000 microns, a leak is
present. Check for leaks and repair. Repeat the
evacuation procedure.
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0 1 2 3 4 5 6 7 8 9 10
LEAK(S)
PRESENT
MINUTES
V
ACU
UM
IN
MI
CR
O
NS
CONDENSIBLES OR SMALL
LEAK PRESENT
NO
LEAKS
NO
CONDENSIBLES
ELECTRICAL CONNECTIONS
HIGH VOLTAGE!
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
.
M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
DUE
TO
ELECTRIC
SHOCK
. W
IRING
MUST
CONFORM
WITH
NEC
OR
CEC
AND
ALL
LOCAL
CODES
. U
NDERSIZED
WIRES
COULD
CAUSE
POOR
EQUIPMENT
PERFORMANCE
,
EQUIPMENT
DAMAGE
OR
FIRE
.
WARNING
T
O
AVOID
THE
RISK
OF
FIRE
OR
EQUIPMENT
DAMAGE
,
USE
COPPER
CONDUCTORS
.
WARNING
GROUNDING REQUIRED!
A
LWAYS
INSPECT
AND
USE
PROPER
SERVICE
TOOLS
. L
ACK
OF
INSPECTION
OR
IMPROPER
TOOLS
MAY
CAUSE
EQUIPMENT
DAMAGE
OR
PERSONAL
INJURY
. A
LL
DISCONNECTED
GROUNDING
DEVICES
MUST
BE
RECONNECTED
BEFORE
INSTALLING
OR
SERVICING
. M
ULTIPLE
COMPONENTS
OF
THIS
UNIT
MAY
CONDUCT
ELECTRICAL
CURRENT
;
THESE
ARE
GROUNDED
. I
F
SERVICING
THE
UNIT
,
ANY
DISCONNECTION
OF
GROUNDING
WIRES
,
SCREWS
,
STRAPS
,
CLIPS
,
NUTS
OR
WASHERS
USED
TO
COMPLETE
THE
GROUND
MUST
BE
RETURNED
TO
THEIR
ORIGINAL
POSITION
AND
PROPERLY
FASTENED
.
CAUTION
Summary of Contents for Amana VZC20
Page 6: ...6...
Page 48: ...48 4 Select YES to continue 5 Select HEAT PUMP 6 Select SYS SETUP...
Page 55: ...55 NOTE BOOST MODE is applicable only for AVZC200 AB and GVZC20 AA or later revision...
Page 56: ...56 https partnerlinkmarketing goodmanmfg com goodman info finder plus...
Page 57: ...57 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 58: ...58 THIS PAGE IS INTENTIONALLY LEFT BLANK...