SERVICING
43
7-SEGMENT DISPLAY
SCREEN 4 (SETTING MODE 2)
Setting
No.
Contents
Setting
Notes
1
Maximum Defrost Interval
0: 30min.
1: 60min.
2: 90min.
3: 120min.
2
Set Maximum Current
N/A
Future Use
3
Vertical Rise
0:Same Level
1:Outdoor Lower
2:Indoor Lower
4
System Verification Test
0:ON
1:OFF
7
Force Defrost Cycle
0:ON
1:OFF
8
Pump Down
0:ON
1:OFF
9
Charge Mode
0:ON
1:OFF
10
Maximum Compressor RPS for Cooling
*
11
Maximum Compressor RPS for Heating
*
12
BOOST MODE Selection
0:ON
, 1:OFF
13
BOOST MODE Temperature
0:105F
, 1:100F, 2:95F,
3:90F, 4:85F, 5:80F, 6:75F,
7:70F, 8:Always ON
NOTE
: Parameters as per factory setting are highlighted in bold and underlined.