SERVICING
29
Air Handler Display (Continued)
LED Display
Menu Description
Menu is enabled if the
is set to 6. (Electric heat will run during the next heat call if the
heat pump fails to satisfy the custom target time for this number of consecutive cycles)
(default = 20 cycles)
Menu is enabled if the
menu is set to 6. (If the addition of low stage electric heat is able
to consecutively satisfy the thermostat under the set target time for this number of cycles,
the system will transition to the heat pump for primary heating)
Menu is enabled if the
menu is set to 6. (This percentage will help determine when
switching back to heat pump only operation is appropriate. Default = 20%. If target time = 20
minutes, the addition of low stage electric heat must statisfy the thermostat by less than 16
minutes. (target time - 20% default = 16 minutes)
View 6 most recent fault codes and Clear Fault Codes if desired (outdoor communicating
units)
Menu is enabled if the
menu is set to 6. Select the target time the system will attempt to
satisfy the thermostat.
Menu is enabled if the
menu is set to 6. Select the percentage past the target time when
the system will enable electric heat operation during heat mode.