SERVICING
32
Upon start up in emergency mode the circuit board may display an “Ed” error. This is an indication that the DIP switches
on the control board need to be configured in accordance with the Electric Heating Airflow Table. Configuring the DIP
switches to the unit will clear the error code.
AVPEC25B14A* AVPEC37C14A* AVPEC59D14A* AVPEC61D14A*
S-9
S-10
S-11
S-12
No Heater
-
-
-
-
OFF*
OFF*
OFF*
OFF*
First
3
5
5
5
ON
ON
ON
ON
Second
5
6
6
6
ON
ON
ON
OFF
Third
6
8
8
8
ON
ON
OFF
ON
Fourth
8
10
10
10
ON
ON
OFF
OFF
Fifth
10
15
15
15
ON
OFF
ON
ON
Sixth
X
19
20
20
ON
OFF
ON
OFF
Seventh
X
X
X
25
ON
OFF
OFF
ON
Switch Bank DS-3
Indoor Control Board Settings
Heater Kit
Selection
Heater kW
Dip Switch Setting
NOTE: Default factory settings are marked with *.
S-21
S-22
OFF*
OFF*
ON
OFF
OFF
ON
ON
ON
S-1
S-2
OFF*
OFF*
ON
OFF
OFF
ON
OFF
OFF
Switch Bank DS-6
Indoor Control Board Settings
Function
Normal operation
Emergency Mode
Cooling Emergency mode/Fan only Emergency mode
Heating Emergency mode (High heat level)
Heating Emergency mode (Low heat level)
Switch Bank DS-2
Outdoor Control Board Settings
Function
Normal operation
Emergency Mode
Cooling Emergency mode (Low cool Level)
Cooling Emergency mode (Medium cool Level)
Cooling Emergency mode (High cool level)