3 Installation
Reciprocating Compressor M Series
3.2 Installation Works
3-5
Illumination
Prepare illumination devices which allow easy operation, cleaning, maintenance, and inspection.
Ventilation
If natural ventilation is insufficient, install ventilation fans according to the regulations.
Cooling
Water
Referring to chapter 7, secure cooling water necessary for your system.
Piping
Table 3-1 Connected piping list
4M
6M
8M
62M
Suction gas
With suction
shut-off valve
4 inch
5 inch
4 inch
Without suction
shut-off valve
ANSI #300
4 inch
ANSI #300
5 inch
ANSI #300
4 inch
Intermediate gas
With suction
shut-off valve
— 3
inch
Without suction
shut-off valve
—
ANSI #300
3 inch
Discharge gas
With suction
shut-off valve
4 inch
5 inch
2½ inch
Without suction
shut-off valve
ANSI #300
4 inch
ANSI #300
5 inch
ANSI #300
2½ inch
High pressure gauge connection port
φ
6
Intermediate pressure gauge
connection port
φ
6
Low pressure gauge connection port
φ
6
Oil pressure gauge connection port
φ
6
Cooling water inlet
20A (Rc3/4)
Cooling water outlet
20A (Rc3/4)
20A (Rc3/4)
Oil separator return inlet
Rc1/2
Safety valve connection port
Rc3/4
Rc1
Rc1¼
High stage: Rc3/4
Low stage: Rc1