If in any moment the door contact closes, the air curtain goes to the selected speed. If the door contact 
opens,  it  will  come  back  to  the  automatic  operating  after  a  delay  time.  The  delay  time  is  selectable 
through switches 5 and 6. 

 
 
 
 
 
 
 
 
 
 
 
CH functions (Hand-Auto): 

 

Anti-frost  thermostat:  When  the  temperature  decreases  below  the  selected  in  the  anti-freezing 
sensor, the fans stop and the electro valve opens (the frost alarm is indicated by a lighted red led and 
the electro valve by a green led). This is to protect the water coil against freezing and it works even 
with  the  air  curtain  stopped.  In  case  of  no  installation  of  the  anti-frost  thermostat,  place  Switch  4  in 
ON position. 

 

Door  contact:      Only  in  automatic  functioning.  When  the  door  opens,  the  air  curtain  changes 
automatically the fan speed to the programmed one (indicated by a lighted orange led). Other type of 
detectors can be used (movement sensors, infrared, etc…). 

 

Room  thermostat:  Modifies  the  ventilation  speed  (and  at  the  same  time  the  heating  power) 
depending on the programmed speed and the switch nº 1. For detailed explanation see the section of 
automatic operating. 

 
 
Programmable switches (controller CH): 

A  block  of  seven  micro  switches  placed  inside  the  controller,  allows  the  customer  to  program  the 
functions of the air curtain as follows:  

 

Switch  1:  It  modifies  the  air  curtain  control  in  automatic  mode  depending  on  the  room  thermostat. 
Detailed explanation in the automatic operating section. 

 

Switch  2:  Door  contact  inverter.  Position  OFF-NO  (normally  open),  position  ON-NC  (normally 
closed). 

 

Switch  3:  Room  thermostat  inverter.  Position  OFF-NO,  position 
ON-NC. 

 

Switch  4:  Anti-frost  thermostat  inverter.  Position  OFF-NC, 
position ON-NO. 

 

Switches  5  and  6:  The  combination  of  these  two  switches 
allows  the  customer  to  set  the  delay  time  to  go  back  to  the 
normal function alter the door is closed. 

 

     

      Switch 5             Switch 6 
          Off 

 

Off         

10 Sec.  

          On            

Off         

40 Sec.  

          Off            

On          

80 Sec.  

          On            

On                   120 Sec. 

 

 

Switch 7: It permits to choose between memory ON/OFF. 

 

Wiring diagrams 
 

Following connection diagrams are enclosed: 
 

 

Warm water heated or only air without regulation. Diagram: AIRDOE11701 

 

Warm water heated or only air with regulation. Diagram: AIRDOE11711 

 

In case you need to connect the equipment to a PLC, the corresponding connections diagrams will be 

supplied.  

 
 

Summary of Contents for MXW 1500 A

Page 1: ...r Curtains MAXWELL SECURITY ADVISE SIMBOLS Attention Danger Safety Advice Danger from electric current of high voltage Injuries risk Danger Do not step underneath Heavy load Important Information AIRD...

Page 2: ...INSTALLATION DIAGRAM WITHOUT REGULATION...

Page 3: ...INSTALLATION DIAGRAM WITH REGULATION...

Page 4: ...roller there is a PCBoard printed circuit located outside the air curtain on the back There is no need to open the unit to connect it Use the telephone cable of 10 meters RJ45 connectors supplied with...

Page 5: ...c device air curtain option with regulation incorporated It is recommended Close the warm water circulation by closing the electro valve to avoid motor overheating while the unit is OFF The electro va...

Page 6: ...ce heavy duty industrial air curtains for vertical and horizontal ins tallations available in 1 5 2 0 and 2 5 meters length Easy dockable modules to reach large dimensions Self supporting galvanized s...

Page 7: ...here is a normally open contact 1 2 that controls the ON OFF of the equipment through any external device The contact is potential free When the contact is Open the air curtain is ON When closed conta...

Page 8: ...speed is the same than the working one the led will change into green Through the internal switches we can modify the time of delay time since the door is closed till it goes back to the normal operat...

Page 9: ...and the switch n 1 For detailed explanation see the section of automatic operating Programmable switches controller CH A block of seven micro switches placed inside the controller allows the customer...

Page 10: ......

Page 11: ......

Page 12: ...am for cleaning the internal parts and components of the air curtain Air curtains don t need any kind of maintenance except the cleaning of the casing and the inlet grille The casing of the air curtai...

Page 13: ...e only original spare parts Fan replacement Before replacing the fan inform people that there is work in progress stop the air curtain through the controller and disconnect main supply Make sure that...

Page 14: ...e is work in progress Disconnect main supply make sure that the unit is without tension and that the fans are stationary Fuse replacement Open the service panel where there is the PCB Remove the fuse...

Page 15: ...ension and the fans are stationary Before removing the screws that fix the coil or heater we have to Remove the screws of the outlet only one side Remove all the lamellas of the outlet and the support...

Page 16: ...ervice panel and empty the water Remove the screws that fix the water coil to the air curtain Tilt the water coil as shown in the picture in order to extract the connection pipes of its holes and pull...

Page 17: ...ontrol never to the Aux Is the fuse of the PCBoard in good conditions Check the fuse and replace it in case it is necessary Type T slow action Some lights of the controller are flashing The green LED...

Page 18: ...d Auto Water control panel Ambient Thermostat Universal controller timer digital display Ready for all type of auxiliary sensors incorporated thermostat automatic operating etc Manual and automatic op...

Page 19: ......

Page 20: ...ense The products that in our eyes have been inadequately used incorrectly manipulated improperly installed connected to different nominal tensions modified repaired by non authorized workers or that...

Reviews: