background image

L

A

MXW 1500

1500

734

MXW 2000

2000

984

MXW 2500

2500

1234

Dimensions

30

615

660

361 150

222

6 x M8

16

16

60

L

A

A

75

60

50

79,5

Model

Airflow

Water

heating 

capacity 

80/60ºC

Water drop 

pressure

80/60ºC

Water 

connections

80/60ºC

Water 

heating 

capacity  

60/40ºC

Water 

drop 

pressure

60/40ºC

Water 

connections

60/40ºC

Fans  

power

230V-50Hz

Fans current

230V-50Hz

               

Noise

 level

(5 m)

              

Weight

m3/h

kW

Pa

kW

Pa

kW

A

dB(A)

kg

MXW 1500 A 

8000

-

-

-

-

-

-

0,68

2,96

59

79

MXW 1500 P 

7000

40,85

14.770

2x1¼”

32,82

15.440

2x1¼”

0,68

2,96

59

95

MXW 2000 A 

12000

-

-

-

-

-

-

1,02

4,44

61

103

MXW 2000 P 

10500

60,66

14.260

2x1¼”

47,87

14.690

2x1¼”

1,02

4,44

61

126

MXW 2500 A 

16000

-

-

-

-

-

-

1,36

5,92

62

126

MXW 2500 P 

14000

78,53

14.690

2x1¼”

63,58

17,950

2x1¼”

1,36

5,92

62

158

MAXWELL | 

Air Curtains For Industrial Doors

•   High performance heavy duty industrial air curtains for vertical and horizontal ins

-

tallations, available in 1.5, 2.0 and 2.5 meters length. Easy dockable modules to 

reach large dimensions.

•   Self-supporting galvanized steel plate housing, powder-coated in white RAL 9016 

as standard.Other colors are available on customer request.

•   High efficiency and low noise axial fans driven with external rotor motor, single 

phase 230V/50Hz. Optionally three phase 400V/50Hz

•   Ambient models “A”, without heating and warm water heated models “P” up to 

120ºC. 

•   Double outlet with Coanda effect to achieve larger and efficient air jet. Adjustable 

pitch angle outlet vanes, airfoil shaped.

•   Different control options, from simple on/off to full automatic: 2/5 ventilation speed, 

manual or automatic functioning, remote control, with telephone cable and fast 

connectors (Plug and Play), interface to connect to BMS, etc...

Characteristics

Specifications

Electrical heated models available on customer request. Let us know your needs

Summary of Contents for MXW 1500 A

Page 1: ...r Curtains MAXWELL SECURITY ADVISE SIMBOLS Attention Danger Safety Advice Danger from electric current of high voltage Injuries risk Danger Do not step underneath Heavy load Important Information AIRD...

Page 2: ...INSTALLATION DIAGRAM WITHOUT REGULATION...

Page 3: ...INSTALLATION DIAGRAM WITH REGULATION...

Page 4: ...roller there is a PCBoard printed circuit located outside the air curtain on the back There is no need to open the unit to connect it Use the telephone cable of 10 meters RJ45 connectors supplied with...

Page 5: ...c device air curtain option with regulation incorporated It is recommended Close the warm water circulation by closing the electro valve to avoid motor overheating while the unit is OFF The electro va...

Page 6: ...ce heavy duty industrial air curtains for vertical and horizontal ins tallations available in 1 5 2 0 and 2 5 meters length Easy dockable modules to reach large dimensions Self supporting galvanized s...

Page 7: ...here is a normally open contact 1 2 that controls the ON OFF of the equipment through any external device The contact is potential free When the contact is Open the air curtain is ON When closed conta...

Page 8: ...speed is the same than the working one the led will change into green Through the internal switches we can modify the time of delay time since the door is closed till it goes back to the normal operat...

Page 9: ...and the switch n 1 For detailed explanation see the section of automatic operating Programmable switches controller CH A block of seven micro switches placed inside the controller allows the customer...

Page 10: ......

Page 11: ......

Page 12: ...am for cleaning the internal parts and components of the air curtain Air curtains don t need any kind of maintenance except the cleaning of the casing and the inlet grille The casing of the air curtai...

Page 13: ...e only original spare parts Fan replacement Before replacing the fan inform people that there is work in progress stop the air curtain through the controller and disconnect main supply Make sure that...

Page 14: ...e is work in progress Disconnect main supply make sure that the unit is without tension and that the fans are stationary Fuse replacement Open the service panel where there is the PCB Remove the fuse...

Page 15: ...ension and the fans are stationary Before removing the screws that fix the coil or heater we have to Remove the screws of the outlet only one side Remove all the lamellas of the outlet and the support...

Page 16: ...ervice panel and empty the water Remove the screws that fix the water coil to the air curtain Tilt the water coil as shown in the picture in order to extract the connection pipes of its holes and pull...

Page 17: ...ontrol never to the Aux Is the fuse of the PCBoard in good conditions Check the fuse and replace it in case it is necessary Type T slow action Some lights of the controller are flashing The green LED...

Page 18: ...d Auto Water control panel Ambient Thermostat Universal controller timer digital display Ready for all type of auxiliary sensors incorporated thermostat automatic operating etc Manual and automatic op...

Page 19: ......

Page 20: ...ense The products that in our eyes have been inadequately used incorrectly manipulated improperly installed connected to different nominal tensions modified repaired by non authorized workers or that...