FAILURES AND SOLUTIONS 

More than 95% of the complaints are submitted during the start of operation of the equipment and are due to 
installations errors.
  

More than 90% of the failures are solved only by checking the connections. Following the three following points, we 
can make sure that the installation is correct: 

A)  Telephone cable is been manipulated: The cable that connects the controller to the air curtain is an 8 lines crossed 

telephone cable. If manipulated (cut or removing the connector) and incorrectly joined, the air curtain won't 
work. 
Moreover, it can damage the electronics. If the connector is joined wrong side, we can solve the problem only 
by turning it (connections diagram of first page). 

B)  Wrong connection of the telephone cable. Verify whether the connector position is correct (between control or 

auxiliary according to the installation diagram, specially if there is more than one air curtain with a single controller.  

C)  Wrong current supply / input. The air curtain input depends on the type of current that is available and also on the 

heating type of the unit. Connect the unit according to the diagram on the first page.

   

 

 

 

 

 

 

Common problems and solutions 

Effect 

Problem 

Solution 

All lights of the 
controller are OFF 

¿Is the telephone cable the 
original (not manipulated), with 
no enlargements either 
shortenings? 

Change the cable or connect it again correctly. 
 

¿Does the current reaches de 
connection box? 

Connect the terminals of the junction box correctly: 
Between L and N there must be 230V and if the air curtain 
goes with a three-phase electrical element, there must be 
400V among the terminals L1,L2 y L3. 

¿Is the controller connected to 
the “Control” of the PCBoard?  

Connect  the  cable  from  the  controller  to  the  “Control”, 
never to the “Aux”.  

¿Is the fuse of the PCBoard in 
good conditions? 

Check the fuse and replace it in case it is necessary (Type 
T, slow action).  

Some lights of the 
controller are 
flashing 
 

The 

green 

LED 

of 

the 

maximum speed flashes  when 
we  stop  the  air  curtain  after 
having  been  operating  with 
heating 

It  is  not  an  error  but  a  safety  mechanism.  The  air  curtain 
turns  on  by  itself  to  the  maximum  speed  to  get  cold  and 
protect its components. When the temperature decreases 
from the safety one, it will stop.  

Some speed or heating lights 
are flashing when the air 
curtain is working.  
 

It  is  a  protection  mechanism  of  the  air  curtain  so  that  the 
internal parts of the air curtain do not suffer damages.  
Situations  on  which  the  problem  continuously  recurs  and 
the way to solve/avoid it: 
1.  Inlet  grille  blocked  (objects,  dirtiness…)  the  ambient 
temperature inside the equipment can increase a loti f the 
air cannot circulate properly. Keep the grille clean.   
2.  Small  room:  We  recommend  installing  a  thermostat  to 
control the heating power  so the protection device  do not 
activates.  
3.  In  case  that  the  ambient  temperature  is  already  high, 
we  recommend  to  lower  the  power  heating  or  install  a 
thermostat.  
4.  Inlet  air  already  warm,  that  comes  from  other  heating 
equipment  beyond  the  air  curtain.  Move  the  air  curtain 
away, place a thermostat in the inlet part of the curtain or 
lower the heating power.  
5. Any motor does not work: inform the technical service. 

The heating is not 
working 

¿Does the three-phase current 
reach the connection box? 

Check installation  

The speed and/or 
the heat change 
continuously with 
no apparent 
reason but the 
lights of the 
controller are not 
flashing.  

Probably the telephone cable 
is near interference sources, 
transmitters, cable plates, 
specially those that supply 
current to the Motors, etc.. 
 

Pass the cable the furthest possible away from the 
interference source, specially when long distances or use 
a screened cable.  
 

Summary of Contents for MXW 1500 A

Page 1: ...r Curtains MAXWELL SECURITY ADVISE SIMBOLS Attention Danger Safety Advice Danger from electric current of high voltage Injuries risk Danger Do not step underneath Heavy load Important Information AIRD...

Page 2: ...INSTALLATION DIAGRAM WITHOUT REGULATION...

Page 3: ...INSTALLATION DIAGRAM WITH REGULATION...

Page 4: ...roller there is a PCBoard printed circuit located outside the air curtain on the back There is no need to open the unit to connect it Use the telephone cable of 10 meters RJ45 connectors supplied with...

Page 5: ...c device air curtain option with regulation incorporated It is recommended Close the warm water circulation by closing the electro valve to avoid motor overheating while the unit is OFF The electro va...

Page 6: ...ce heavy duty industrial air curtains for vertical and horizontal ins tallations available in 1 5 2 0 and 2 5 meters length Easy dockable modules to reach large dimensions Self supporting galvanized s...

Page 7: ...here is a normally open contact 1 2 that controls the ON OFF of the equipment through any external device The contact is potential free When the contact is Open the air curtain is ON When closed conta...

Page 8: ...speed is the same than the working one the led will change into green Through the internal switches we can modify the time of delay time since the door is closed till it goes back to the normal operat...

Page 9: ...and the switch n 1 For detailed explanation see the section of automatic operating Programmable switches controller CH A block of seven micro switches placed inside the controller allows the customer...

Page 10: ......

Page 11: ......

Page 12: ...am for cleaning the internal parts and components of the air curtain Air curtains don t need any kind of maintenance except the cleaning of the casing and the inlet grille The casing of the air curtai...

Page 13: ...e only original spare parts Fan replacement Before replacing the fan inform people that there is work in progress stop the air curtain through the controller and disconnect main supply Make sure that...

Page 14: ...e is work in progress Disconnect main supply make sure that the unit is without tension and that the fans are stationary Fuse replacement Open the service panel where there is the PCB Remove the fuse...

Page 15: ...ension and the fans are stationary Before removing the screws that fix the coil or heater we have to Remove the screws of the outlet only one side Remove all the lamellas of the outlet and the support...

Page 16: ...ervice panel and empty the water Remove the screws that fix the water coil to the air curtain Tilt the water coil as shown in the picture in order to extract the connection pipes of its holes and pull...

Page 17: ...ontrol never to the Aux Is the fuse of the PCBoard in good conditions Check the fuse and replace it in case it is necessary Type T slow action Some lights of the controller are flashing The green LED...

Page 18: ...d Auto Water control panel Ambient Thermostat Universal controller timer digital display Ready for all type of auxiliary sensors incorporated thermostat automatic operating etc Manual and automatic op...

Page 19: ......

Page 20: ...ense The products that in our eyes have been inadequately used incorrectly manipulated improperly installed connected to different nominal tensions modified repaired by non authorized workers or that...

Reviews: