User Manual – 16 V and 48 V Modules 

– Doc. No. 1008491.13 

© 2014 Maxwell Technologies, Inc. 

 

Page 7

 

f

TH

ESR

d

R

R

I

T

2

 

where

I

 = 

RMS current (amps)

 

R

ESR

 =  

equivalent series resistance

R

DC

 

(ohms)

 

R

TH

 = 

thermal resistance (

o

C/W)

 

d

f

 = 

duty cycle fraction

 

The 

T  value  calculated  above  plus  ambient  temperature  should  remain  below  the  specified 

maximum  operating  temperature  for  the  module  (please  refer  to  the  module  datasheet)  as 

measured  by  the  thermistor  output.    If  active  cooling  methods  are  employed,  it  is  possible  to 

operate at higher currents or duty cycles than if only passive cooling is utilized.  
 

4.

 

Operation

 

 

The module should only be operated within specified voltage and temperature ratings.  Determine 

whether  current  limiting  is  necessary  based  on  the  current  ratings  of  attached  components.  

Observe polarity indicated on module.  Do not reverse polarity. 

 

5.

 

 

Safety 

DANGER 

 

HIGH VOLTAGE HAZARD 

Never touch the power terminals as the module can be charged and 

cause 

fatal electrical shocks

. Always verify that the module is fully 

discharged before manipulating the module. Refer to the instructions 

below for the manual discharge procedure. 

 

 

Do not operate unit above the specified voltage. 

 

Do not operate unit above the specified temperature rating. 

 

Do not touch terminals with conductors while charged.  Serious burns, 

shock, or material fusing may occur. 

 

Protect surrounding electrical components from incidental contact. 

 

Provide sufficient electrical isolation when working above 50 V DC. 

 

Prior to installation on or removal from the system, it is mandatory to 

fully discharge the module to guarantee the safety of all personnel. 

 

 

 

 

 

 

Downloaded From  

Oneyac.com

Summary of Contents for 16 V Series

Page 1: ...and their respective designs and or logos are either trademarks or registered trademarks of Maxwell Technologies Inc and may not be copied imitated or used in whole or in part without the prior writt...

Page 2: ...ach module contains one temperature monitor output in the form of an NTC thermistor 2 Unpacking and Handling Unpacking 2 1 Inspect the shipping carton for signs of damage prior to unpacking the module...

Page 3: ...ages in excess of 60 V appropriate protection and sealing should be used on both module terminals to avoid shock hazards and corrosion A proper installation should not exert any bending or twisting to...

Page 4: ...dards for the application The anodized coating of the module on the ground connection surface should be removed to ensure an optimal electrical contact Apply a layer of high conductivity anti oxidant...

Page 5: ...modules to prevent undesirable lateral forces on the terminals The energy storage modules have low ESR As a result the resistance of the wires connecting the energy storage module to the application...

Page 6: ...pplied with the module Note The passive version suffix B02 of the BMOD0500 only provides the output of the NTC thermistor for the temperature monitor signal There is no voltage monitoring signal in th...

Page 7: ...istance of the thermistor varies with temperature to provide the actual temperature of the module The thermistor is located inside the module Under normal operating conditions the temperature output s...

Page 8: ...necessary based on the current ratings of attached components Observe polarity indicated on module Do not reverse polarity 5 Safety DANGER HIGH VOLTAGE HAZARD Never touch the power terminals as the m...

Page 9: ...e for example the BK Precision DC Electronic Load Model 8500 or a similar tool 3 If the voltage is under 2V connect the shorting wire provided by Maxwell to the and connectors 4 The module is now safe...

Page 10: ...o avoid false signals or shock hazards In high vibration environments do this every 6 months and in low vibration environments do this annually 7 Storage The discharged module can be stored in the ori...

Page 11: ...ell Technologies Korea Co Ltd Room 1524 D Cube City Office Tower 15F 662 Gyeongin Ro Guro Gu Seoul 152 706 South Korea Phone 82 10 4518 9829 Maxwell Technologies Shanghai Trading Co Ltd Unit A2 C 12th...

Page 12: ...Maxwell Technologies Downloaded From Oneyac com...

Reviews: