User Manual – 16 V and 48 V Modules 

– Doc. No. 1008491.13 

© 2014 Maxwell Technologies, Inc. 

 

Page 3

 

 

Electrical 

3.2

 

WARNING 

 

 

To avoid arcing the energy storage module should be in a 
discharged state and the system power disconnected during 
installation.  The module is shipped discharged and with a shorting 
wire.  The shorting wire should be removed prior to electrical 
connections. 

 

To provide the lowest possible ESR the energy storage modules are 
not fused.  Care should be taken within the application to prevent 
excessive current flow as required.  Excessive current and/or duty 
cycle will result in overheating the module which will cause 
irreparable damage.  Please consult the specific data sheet for each 
module for current and duty cycle capabilities. 

 

Module-to-module cabling should be sized for the applications peak and/or RMS current. 

Undersized cables may cause excessive cable or interconnect temperature rise and system 

electrical resistance. High resistance wiring/cables or module power connections will increase 

terminal cell temperature and degrade module lifetime and long term performance. Reference 

applicable wire sizing guides. Wire temperature must not exceed module temperature.  

Note: 

The module chassis should be grounded to the system chassis through any of the module 

mounting  holes.  Refer  to  applicable  ground  wiring  guides  and  standards  for  the  application.

  

 

The  anodized  coating  of  the  module  on  the  ground  connection  surface  should  be  removed  to 

ensure an optimal electrical contact. Apply a layer of high conductivity anti-oxidant joint compound 

between the mating surfaces (IDEAL Noalox

®

 Anti-Oxidant Compound or equivalent). 

3.2.1

 

Output Terminal Posts 

 

The  output  terminals  of  the  module  consist  of  internally  threaded  aluminum  posts.    They  are 

designed to connect directly to a ring lug or a bus bar.  Maximum thread depth is 20 mm.    If ring 

terminals and lock washers in excess of 10 mm are to be used, a longer bolt must be selected.  In 

no instance should the total amount of thread engagement be less than 10 or greater than 20 mm.   

 
The  terminal  contact  surface  should  be  cleaned  with  a  light  abrasive  such  as  Scotch-Brite

TM

  to 

remove any oxidation.  Apply a layer of high conductivity anti-oxidant joint compound between the 

mating surfaces (IDEAL Noalox

®

 Anti-Oxidant Compound or equivalent).  The positive terminal is 

threaded for M8 x 1.25 steel bolts.  The negative terminal is threaded for M10 x 1.5 steel bolts.  

Lock  washers  are  required  for  long  term,  reliable  connections.    For  additional  performance,  a 

thread locking compound such as Loctite

®

 425 may be used.  However, care should be taken that 

the thread locking compound does not come in contact with the electrical mating surfaces. 

 

When tightening the terminal bolts, a torque of 20 N-m / 14.8 ft-lbs for the M8 and 30 N-m / 22.1 

ft-lbs for the M10 bolts should be used.  Do not exceed recommended torque. 

 

Downloaded From  

Oneyac.com

Summary of Contents for 16 V Series

Page 1: ...and their respective designs and or logos are either trademarks or registered trademarks of Maxwell Technologies Inc and may not be copied imitated or used in whole or in part without the prior writt...

Page 2: ...ach module contains one temperature monitor output in the form of an NTC thermistor 2 Unpacking and Handling Unpacking 2 1 Inspect the shipping carton for signs of damage prior to unpacking the module...

Page 3: ...ages in excess of 60 V appropriate protection and sealing should be used on both module terminals to avoid shock hazards and corrosion A proper installation should not exert any bending or twisting to...

Page 4: ...dards for the application The anodized coating of the module on the ground connection surface should be removed to ensure an optimal electrical contact Apply a layer of high conductivity anti oxidant...

Page 5: ...modules to prevent undesirable lateral forces on the terminals The energy storage modules have low ESR As a result the resistance of the wires connecting the energy storage module to the application...

Page 6: ...pplied with the module Note The passive version suffix B02 of the BMOD0500 only provides the output of the NTC thermistor for the temperature monitor signal There is no voltage monitoring signal in th...

Page 7: ...istance of the thermistor varies with temperature to provide the actual temperature of the module The thermistor is located inside the module Under normal operating conditions the temperature output s...

Page 8: ...necessary based on the current ratings of attached components Observe polarity indicated on module Do not reverse polarity 5 Safety DANGER HIGH VOLTAGE HAZARD Never touch the power terminals as the m...

Page 9: ...e for example the BK Precision DC Electronic Load Model 8500 or a similar tool 3 If the voltage is under 2V connect the shorting wire provided by Maxwell to the and connectors 4 The module is now safe...

Page 10: ...o avoid false signals or shock hazards In high vibration environments do this every 6 months and in low vibration environments do this annually 7 Storage The discharged module can be stored in the ori...

Page 11: ...ell Technologies Korea Co Ltd Room 1524 D Cube City Office Tower 15F 662 Gyeongin Ro Guro Gu Seoul 152 706 South Korea Phone 82 10 4518 9829 Maxwell Technologies Shanghai Trading Co Ltd Unit A2 C 12th...

Page 12: ...Maxwell Technologies Downloaded From Oneyac com...

Reviews: