5 Inputs and Outputs
5.1 Inputs
5.1.1
Set value “Set”
The set value can be applied externally via an analogue voltage or internally
using potentiometer
P3
.
If the set value is applied externally using the “+Set” and “-Set” connections,
DIP switch
S9
must be in the “ON
Ð
” position
.
Two different ranges can be selected to apply an external analogue set value.
The required range is determined by the position of DIP switch
S10
.
Set value range -10 ... +10 V
Input voltage range
-10 ... +10V
Input
wiring
differential
Input impedance
200 k
Ω
(differential)
positive set value
(+Set) > (-Set)
positive motor voltage or current
negative set value
(+Set) < (-Set)
negative motor voltage or current
DIP
switch
S10
OFF
Ï
DIP switch
S9
ON
Ð
Use of external potentiometer
Set value range -3.9 ... +3.9 V Input voltage range
-3.9 ... +3.9 V
Input
wiring
differential
Input impedance
200 k
Ω
(differential)
positive set value
(+Set) > (-Set)
positive motor voltage or current
negative set value
(+Set) < (-Set)
negative motor voltage or current
DIP
switch
S10
ON
Ð
DIP switch
S9
ON
Ð
recommended
potentiometer
50 k
Ω
(linear)
Use of internal potentiometer P3
If the set value is adjusted internally via potentiometer
P3
, DIP switch
S9
must
be in the “OFF
Ï
” position.
P3
= 50 ... 100 % (right end stop)
positive motor voltage or current
P3
= 50 ... 0 % (left end stop)
negative motor voltage or current
Input wiring
(+Set) = (-Set)
short-circuited
DIP
switch
S10
optional
DIP switch
S9
OFF
Ï
8