matrix III led continued
Matrix III LED
Problem Condition
Solution(s) for
Problem Condition
Normal
LED
“ID PLUG” LED is FLASHING and board beeping
“SOLAR MODE” LED is ON
“OPEN/CLS” LED is ON
“OPEN/CLS” LED is FLASHING
“MOTOR OVERLOAD” LED is ON
“EXIT” LOOP LED is FLASHING or
constantly ON
“SAFETY” LOOP LED is FLASHING or
constantly ON
“GATE DISABLE” LED is ON
“MAG LOCK” LED is FLASHING
“GATE TAMPER” LED is FLASHING
“12VDC” LED is OFF. “24VDC” LED is OFF
“SLIDER LIMIT” LED is ON
“ON/OFF BATTERY” LED is OFF
“QUICK CLOSE” LED is ON
“GATE SPEED” LEDs are ON but gate moves
slowly.
•
Insert ID PLUG module that is tethered to chassis into “ID PLUG” connector.
•
Operator is being powered by solar panel ONLY.
•
Sensor on OPEN/CLS input (photocell or edge) may have detected an obstruction while opening or
closing gate.
•
Photocell on OPEN/CLS input is misaligned with reflector.
•
Sensor on OPEN/CLS input (photocell or edge) may not be wired properly, (see ).
•
Sensor is NOT a N.C. monitored sensor that is UL325 2018 compliant.
•
Sensor on OPEN/CLS is damaged or malfunctioning.
•
Sensor might need to be re-learned.
•
Check if gate is binding against catch post or bracket in opened or closed position.
•
Check if gate moves manually with low resistance throughout its full range of motion.
•
Check if chain is installed inline with idle wheels in both OPEN and CLOSED positions.
•
Loop fault condition: Check if EXIT loop wires are connected into to loop input connector properly.
•
Check if loop detector is inserted properly in Loop Rack slot.
•
Set unique loop detector frequency for each loop detector used.
•
Loop Detector might be defective. Replace defective loop detector.
NOTE: RENO loop detector LED’s flash as default, but function normally (ignore the flashing).
•
Loop fault condition: check if SAFETY loop wires are connected into to loop input connector properly.
•
Check if SAFETY loops are wired in series.
•
Check if loop detector is inserted properly in Loop Rack slot.
•
Set unique loop detector frequency for each loop detector used.
•
Loop Detector might be defective. Replace defective loop detector.
NOTE: RENO loop detector LED’s flash as default, but function normally (ignore the flashing).
•
Check if “Gate Shut-off” switch is ON, Turn it OFF. If it is OFF, cycle the switch (ON then OFF).
•
Check if the chain is dropped. If so, gate is disabled for safety. Re-install chain and cycle the "Gate
Shut-off" switch (ON then OFF) to enable operator.
•
Check if an external device is triggering GATE DISABLE input. Disconnect devices individually to
determine possible false triggering of GATE DISABLE.
•
Maglock power is lost. Check if maglock power transformer is wired properly or needs to be replaced.
•
Switch is set to delay but no maglock is connected. Set switch to OFF
•
Gate was manually moved off of its CLOSED position causing Tamper Relay to trigger for few seconds.
•
Check for a short in wiring to connected device. DO NOT power external keypads or telephone entry to
this port (only use for radio receiver / photocell).
•
Only ON if factory installed plug is plugged in. Re-install plug into SWING LIMIT connection for swing
gate operator.
•
Batteries are turned OFF. Turn toroid box AC POWER switch ON and batteries automatically turn ON.
•
Quick Close feature is turned ON. If this feature is not desired, turn quick close OFF.
•
Check if OPEN and CLOSE Limits have been learned. Refer to “Learn Gate Positions” (see ).
•
ONLY Maximum settings will turn LEDs ON. All other settings, LEDs remain OFF.
OFF
12
OFF
13
OFF
31
OFF
8
OFF
15
OFF
17
OFF
35
OFF
28
OFF
34
ON
18 or 19
OFF
21
ON
22
OFF
23
ON
42
5
7
22
UL 325 2018 Standard - MAX 1500 PRO/2200 PRO/F18 PRO Matrix III Install Version 7